background image

8 Technical data

Installation manual

23

EBLQ+EDLQ011~W1
Daikin Altherma low temperature monobloc
4P522031-1 – 2018.01

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do in relation to maintaining the unit.

▪ Explain  the  user  about  energy  saving  tips  as  described  in  the

operation manual.

7.1

About locking and unlocking

If  required,  it  is  possible  to  lock  the  buttons  of  the  main  user
interface, making it impossible for the user to operate it. For the user
to  be  able  to  change  setpoint  temperatures,  the  simplified  user
interface or an external room thermostat is then required.

You can use the following locking modes:

▪ Function  lock:  Locks  a  specific  function  to  prevent  people  from

changing its settings.

▪ Button  lock:  Locks  all  buttons  to  prevent  users  from  changing

settings.

To activate or deactivate a function lock

1

Press 

 to go to the menu structure.

2

Press 

 for more than 5 seconds.

3

Select a function and press 

.

4

Select Lock or Unlock, and press 

.

To activate or deactivate button lock

1

Press 

 to go to one of the home pages.

2

Press 

 for more than 5 seconds.

8

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin extranet (authentication required).

8.1

Piping diagram: Outdoor unit

M

t >

R5T t >

R3T t >

R4T

1

1

2

3

4

5

6

7

8

9

12

28

13

29

16

20

18

17

26

27

21

24

25

32

33

24

23

31

36

14

26

32

16

15

(V3)

30

19

R6T

R1T

Y1E

Y3E

Y3S

R5T

34

34

A

B

R1T

10

t >

R3T

11

t >

t >

R4T

t >

t >

t >

3D115219

E1HC

35

C

D

1

Shut‑off valve with drain/fill valve

2

Flow switch

3

Pump

4

Flow sensor

5

Air purge

6

Plate heat exchanger

7

Safety valve

8

Water filter

9

Expansion vessel

10

Outlet water heat exchanger thermistor

11

Refrigerant liquid side thermistor

12

Inlet water thermistor

13

Gas stop valve with service port

14

Electronic expansion valve (main)

15

4‑way valve

16

Muffler (lower muffler on diagram: only for V3)

17

High pressure switch

18

Compressor

19

Pressure sensor

20

Accumulator

21

Service port 5/16" flare

22

Heat exchanger

23

Fan motor (propeller fan)

24

Capillary tube

25

Distributor

26

Refrigerant filter

27

Solenoid valve

28

Liquid stop valve with service port

29

Suction pipe thermistor

30

Discharge pipe thermistor

31

Outdoor air temperature thermistor

32

Heat exchanger thermistor (middle)

33

Heat exchanger thermistor (distributor)

34

Liquid pipe thermistor

35

Crankcase heater

36

Electronic expansion valve (injection)

A

Water side

B

Refrigerant side

C

Outlet

D

Inlet
Field installed
Refrigerant flow - cooling

Summary of Contents for Altherma EBLQ014CAV3

Page 1: ...ow temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ011CAV3 EBLQ014CAV3 EBLQ016CAV3 EBLQ011CAW1 EBLQ014CAW1 EBLQ016CAW1 EDLQ011CAV3 EDLQ014CAV3 EDLQ016CAV3...

Page 2: ...B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU...

Page 3: ...sti za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uv...

Page 4: ...py the system settings from the first to the second user interface 14 5 1 4 To copy the language set from the first to the second user interface 15 5 1 5 Quick wizard Set the system layout after first...

Page 5: ...5 C in domestic hot water operation mode 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into t...

Page 6: ...m flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely cont...

Page 7: ...nd washers field supply as follows 150 6 2 0 350 3 4 5 3 5 5 a mm 2 6 1 5 6 M12 a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is...

Page 8: ...n places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rub...

Page 9: ...ng Prevent from freezing 5 C 10 15 10 C 15 25 15 C 20 35 20 C 25 25 C 30 NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table a...

Page 10: ...ter field supply indicates a pressure of 2 0 bar 5 Purge as much air as possible from the water circuit For instructions see 6 Commissioning on page 21 6 Refill the circuit until the pressure is 2 0 b...

Page 11: ...emove reposition the switch box and gain access to other components during service CAUTION Do NOT push or place redundant cable length in the unit 4 4 2 To connect the main power supply 1 Connect the...

Page 12: ...4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring re...

Page 13: ...er NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in...

Page 14: ...other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result...

Page 15: ...tion select Confirm layout and press Confirm layout Please confirm the system layout The system will restart and will be ready for first startup OK Cancel Confirm Adjust 5 The user interface re initia...

Page 16: ...d backup heater Backup heater EKMBUHCA3V3 can only be configured to be a 3V3 backup heater Unified backup heater EKMBUHCA9W1 can be configured in 4 ways 3V3 1 230 V 1 step of 3 kW 6V3 1 230 V 1st step...

Page 17: ...sensor connected to option box EK2CB07CAV3 INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor Code Description A 2 2 F 6 D 04 PCC by digital inputs 0 No 1 Y...

Page 18: ...aximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water tempera...

Page 19: ...ature at the hot water taps INFORMATION There is a risk of space heating cooling capacity shortage comfort problem in case of frequent domestic hot water operation frequent and long space heating cool...

Page 20: ...thod Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room the...

Page 21: ...it The shut off valves are properly installed and fully open The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume i...

Page 22: ...sure the room temperature control the leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuato...

Page 23: ...es 2 Press for more than 5 seconds 8 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is avail...

Page 24: ...actory setting of all switches OFF 4 Legend A1P Printed circuit board main A2P V3 only Printed circuit board service A2P W1 only Printed circuit board inverter A3P Printed circuit board noise filter A...

Page 25: ...hydro switch box Use normal kWh rate power supply for hydro switch box A1P Main PCB A2P Current loop PCB English Translation B1L Flow sensor E11H Flextube heater 15 6 W E12H Expansion vessel heater 50...

Page 26: ...ckup heater F1T F2T Thermal fuse backup heater F1U Fuse T 5 A 500 V backup heater option K1M Contactor backup heater step 1 English Translation K1R Relay backup heater step 1 K2M Contactor backup heat...

Page 27: ...om thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity...

Page 28: ...4P522031 1 2018 01 Copyright 2018 Daikin 4P522031 1 0000000B...

Reviews: