7 Installation
Installer reference guide
32
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1D – 2018.07
2×
2
a
a
1
a
Air outlet
NOTICE
The pedestal MUST be aligned with the backside of the
U‑beam.
3
Remove the protective cardboard and instruction sheet.
b
a
a
Protective cardboard
b
Instruction sheet
7.3.5
To provide drainage
▪ Avoid installation places where water leaking from the unit due to
a blocked drain pan can cause damage to the location.
▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
NOTICE
If the drain holes of the outdoor unit are blocked up,
provide space of at least 300 mm below the outdoor unit.
An additional drain pan kit (EKDP008CA) can be used to gather the
drain water. The drain pan kit consists of:
b
a
a
Drain pan
b
U-beams
283 mm
580 mm
INFORMATION
If you install the drain pan kit (with or without drain pan
heater) in combination with the low sound cover
(EKLN08A1), different installation instructions apply for the
drain pan kit. See the installation manual of the low sound
cover.
a
b
d
c
c
b
a
Low sound cover
b
Bottom parts of the low sound cover
c
Drain pan kit
d
Drain pan heater