8 Configuration
Installer reference guide
62
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1D – 2018.07
#
Code
Description
Changeover settings related to the indoor temperature. ONLY
applicable when Automatic is selected and the system is configured
in room thermostat control with 1 leaving water temperature zone
and quick heat emitters.
N/A
[4-0B]
Hysteresis: Ensures that changeover is
ONLY done when necessary.
Example:
The space operation mode ONLY
changes from cooling to heating when
the room temperature drops below the
desired heating temperature subtracted
by the hysteresis.
Range: 1°C~10°C, step 0.5°C (default:
1°C)
N/A
[4-0D]
Offset: Ensures that the active desired
room temperature can be reached.
Example: if heating to cooling
changeover would occur below the
desired room temperature in heating, this
desired room temperature could never
be reached.
Range: 1°C~10°C, step 0.5°C (default:
3°C)
8.3.2
Domestic hot water control: advanced
Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled
or sch reheat.
You can define preset tank temperatures:
▪ storage economic
▪ storage comfort
▪ reheat
▪ reheat hysteresis
Preset values make it easy to use the same value in the schedule. If
you later want to change the value, you only have to do it in 1 place
(see also operation manual and/or user reference guide).
Storage comfort
When programming the schedule, you can make use of the tank
temperatures set as preset values. The tank will then heat up until
these setpoint temperatures have been reached. Additionally, a
storage stop can be programmed. This feature puts a stop to tank
heating even if the setpoint has NOT been reached. Only program a
storage stop when tank heating is absolutely undesirable.
#
Code
Description
[7.4.3.1]
[6-0A]
30°C~[6‑0E]°C (default: 60°C)
Storage eco
The storage economic temperature denotes the lower desired tank
temperature. It is the desired temperature when a storage economic
action is scheduled (preferably during day).
#
Code
Description
[7.4.3.2]
[6-0B]
30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat
The desired reheat tank temperature is used:
▪ in reheat mode of scheduled + reheat mode: The guaranteed
minimum tank temperature is set by T
HP OFF
–[6‑08], which is either
[6‑0C] or the weather dependent setpoint, minus the reheat
hysteresis. If the tank temperature drops below this value, the tank
is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature raises above this value,
domestic hot water preparation and space heating/cooling are
executed sequentially.
#
Code
Description
[7.4.3.3]
[6-0C]
30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat hysteresis
Only applicable when domestic hot water preparation is sch
reheat.
#
Code
Description
N/A
[6-08]
2°C~20°C (default: 10°C)
Weather dependent
The weather dependent installer settings define the parameters for
the weather dependent operation of the unit. When weather
dependent operation is active the desired tank temperature is
determined automatically depending on the averaged outdoor
temperature: low outdoor temperatures will result in higher desired
tank temperatures as the cold water tap is colder and vice versa. In
case of scheduled or screheat domestic hot water
preparation, the storage comfort temperature is weather dependent
(according to the weather dependent curve), the storage economic
and reheat temperature are NOT weather dependent. In case of
reheat only domestic hot water preparation, the desired tank
temperature is weather dependent (according to the weather
dependent curve). During weather dependent operation, the end-
user cannot adjust the desired tank temperature on the user
interface.
#
Code
Description
[A.4.6]
N/A
Weather dependent desired tank
temperature is:
▪ Fixed (default): disabled. All desired
tank temperature are NOT weather
dependent.
▪ Weather dep.: enabled. In scheduled
or
screheat
mode,
the
storage
comfort
temperature
is
weather dependent. Storage economic
and reheat temperatures are NOT
weather dependent. In reheat mode,
the desired tank temperature is
weather dependent.
Note:
When the displayed tank
temperature is weather dependent, it
cannot be adjusted on the user
interface.