9/9
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.I
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: Forced off
1: As normal
9.I
[D-07]
R/O
0: No
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-0A]
0
9.I
[D-0B]
2
9.I
[E-00]
R/O
0~5
0: LT split
9.I
[E-01]
R/O
0
9.I
[E-02]
R/O
1: Heating only
9.I
[E-03]
R/O
2: 3V (*1)
3: 6V (*2)
4: 9W (*3)
9.I
[E-04]
R/O
0: No
1: Yes
9.I
[E-05]
R/O
0: No
1: Yes
9.I
[E-06]
R/O
0: No
1: Yes
9.I
[E-07]
R/O
1: Integrated
9.I
[E-08]
R/O
1: Enabled
9.I
[E-09]
1
9.I
[E-0A]
0
9.I
[E-0B]
R/O
1: Yes
9.I
[E-0C]
0
9.I
[E-0D]
0
9.I
[E-0E]
0
9.I
[F-00]
R/W
0: Disabled
1: Enabled
9.I
[F-01]
20
9.I
[F-02]
R/W
3~10°C, step: 1°C
3°C
9.I
[F-03]
R/W
2~5°C, step: 1°C
5°C
9.I
[F-04]
R/W
0: No
1: Yes
9.I
[F-05]
0
9.I
[F-09]
R/W
0: Disabled
1: Enabled
9.I
[F-0A]
0
9.I
[F-0B]
R/W
0: No
1: Yes
9.I
[F-0C]
1
9.I
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
What is the pump operation mode?
Is a bottom plate heater connected?
--
Pump operation during flow abnormality.
--
Close shut-off valve during thermo OFF?
Is a bi-zone kit installed?
--
Bottom plate heater ON temperature.
Bottom plate heater hysteresis.
Can the system prepare domestic hot water?
Is a DHW tank installed in the system?
What kind of DHW tank is installed?
Power saving function for outdoor unit.
--
--
--
Is the power saving function available on the outdoor unit?
Pump operation allowed outside range.
Is glycol present in the system?
--
--
Which type of unit is installed?
Is an external kWh meter used for power measurement?
What is the indoor unit software type?
What is the number of backup heater steps?
Which type of compressor is installed?
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
--
Leaving water temperature compensation around 0°C.
Which type of DHW pump is installed?
--
(*1) *3V_
(*2) *6V_
(*3) *9W
(#) Setting is not applicable for this unit.
4P495259-1A - 2017.11