12.4.1 Air Handler Only (Non-Heat Kit Models)

IMPORTANT: Installation of Air Handler must follow any 

local codes/regulations. The manufacture recommends 

that when a heater kit is not installed, a field supplied 

disconnect switch or breaker should be installed in the 

electrical circuit that will allow power to be shut-off for 

service or maintenance.

The building supply connects to the stripped black and red 

wires contained in the air handler electrical compartment 

cavity. A ground screw is also contained in this area.  

Attach the Supply wires to the air handler conductors as 

shown in the unit wiring diagram using appropriately sized 

solderless connectors or other NEC or CEC approved 

means.

12.4.2 Air Handler - Non-Circuit Breaker Heat Kits

A terminal block is provided with the HKS and HKTSD kit 

to attach the power supply and air handler connections. 

Follow the HKS and HKTSD Installation Manual and wiring 

diagram for complete wiring details. 

12.4.3 Air Handler With Circuit Breaker Heat Kit

The air handler has soft plastic cover on the upper access 

panel and can be removed to allow the heater kit circuit 

breaker to be installed. The circuit breakers have lugs 

for power supply connection. See the HKS and HKTSD 

Installation Instructions for further details. 

12.5 Low Voltage Connections

Several combinations of low voltage schemes are possible, 

depending on the presence of a heat kit and whether the 

heat kit is single-stage or multi-stage, whether the outdoor 

section is an air conditioner or heat pump, and whether 

the outdoor section is single-stage or two-stage. The 

24V-control voltage connects the air handler to the room 

thermostat and condenser.  Low voltage wiring must be 

copper conductors. A minimum of 18AWG must be used 

for installations up to 100 feet. Low voltage wiring must 

be connected through the top of the cabinet or either side.  

See the “Thermostat Wiring” section of this manual for 

typical low voltage wiring connections.

12.5.1 Thermostats

Second-stage heat can be accomplished by a multi-stage 

heating thermostat or the addition of an outdoor thermostat 

as shown in wiring schematics on page 19.  Follow the 

thermostat manufacturer’s instructions for installation.

12.6 Speed Tap Adjustment

AMST**U1400** air handlers feature 9-speed energy 

efficient blower motors. The motors run at a constant 

torque with very low power consumption. Changing the 24 

VAC leads to the desired speed tap on the terminal block 

will adjust provided CFM (speed tap adjustment of the 

AMST60DU1400** is not supported). 

The AMST blower motor speeds are programmed to deliver 

adequate airflow at rated external static pressure and 

with a 60 second off time delay. For details, refer to the 

specification sheet applicable to your model.

12.6.1 Selecting Speed Taps 1-5 (Not applicable to 

AMST60DU1400**)

When selecting Speed Taps 1-5, move the Purple (PU) 

wire lead from the alternate control relay to the desired 

Speed Tap (Note: The labeled terminal block (TB) locations 

T1-T5 correlate to Speed Taps 1-5). See Table 12.

NOTE: When selecting Speeds Tap 1 or 5, the Black 

(BK) jumper should be removed completely and placed 

in the Literature Bag. 

OR

WH

BR

PU

YL

T1

T2

T3

T4

T5

TB Engaged

Tap-1

PU

T1

Tap-2

PU

T2

Tap-3

PU

T3

Tap-4

PU

T4

Tap-5

PU

T5

Table 12

Speed Taps 1-5 Wiring 

Figure 13

Summary of Contents for AMST U1400 Series

Page 1: ...ice Inspection 12 12 2 Wire Sizing 12 12 3 Maximum Overcurrent Protection MOP 12 12 4 Electrical Connections Supply Voltage 13 12 4 1 Air Handler Only Non Heat Kit Models 13 12 4 2 Air Handler Non Cir...

Page 2: ...d the danger of CO poisoning which can occur if a carbon monoxide producing device con nues to operate in the enclosed area Carbon monoxide emissions can be re circulated throughout the structure if t...

Page 3: ...Shipping Material Removal IMPORTANT All Shipping Material used to protect the equipment and the equipment s components during transit should be removed before final installation 2 3 1 Blower Support...

Page 4: ...stall units such that a positive slope in condensate line 1 4 per foot is allowed 5 5 Horizontal Applications If installed above a finished living space a secondary drain pan as required by many build...

Page 5: ...LUG KIT Table 1 SIDE DRAIN PAN DPK1 DRAIN PLUG COIL ACCESS PANEL MAIN DRAIN PAN Drain Pan Figure 1 1 Side Drain Pan Removal Figure 2 6 2 Horizontal Left Installation Figure 5 No field modifications ar...

Page 6: ...available through your local distributor The kits are not supplied with the air handler and must be used to assist with condensation management in humid environment applications The individual instal...

Page 7: ...ssemblies NOTE The use of a heat shield is strongly recommended when brazing to avoid burning the serial plate or the finish of the unit Heat trap or wet rags must be used to protect heat sensitive co...

Page 8: ...ng Panel Internal Part Terminology Figure 7 External Part Terminology Figure 8 Coil Installation For Downflow Figure 9 Access Panel Configuration for Downflow or Horizontal Right Figure 10 Important N...

Page 9: ...d superheat of 8 F 1 F If subcooling and superheat are low adjust TXV to 8 F 1 F superheat then check subcooling a If subcooling is low and superheat is high add charge to raise subcooling to 8 F 1 F...

Page 10: ...ttention CAUTION If secondary drain is not installed the secondary access must be plugged Insulate drain lines located inside the building or above a finished living space to prevent sweating Install...

Page 11: ...dimension must be less than 23 x20 filter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number 11 Electric Heat Refer to the installation man...

Page 12: ...In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 12 1 Building Electrical Service Inspection This unit is designed for single phase electrical supply onl...

Page 13: ...C approved strain relief is to be used at this entry point Some codes municipalities require the supply wire to be enclosed in conduit Consult your local codes Side of Cabinet Top of Cabinet KNOCK OUT...

Page 14: ...tdoor section is single stage or two stage The 24V control voltage connects the air handler to the room thermostat and condenser Low voltage wiring must be copper conductors A minimum of 18AWG must be...

Page 15: ...BK T1 T3 Tap 8 BK PU BK T1 T4 Tap 9 BK PU BK T1 T5 Table 13 Speed Taps 6 9 Wiring Figure 14 12 6 3 AMST60DU1400 ONLY For high static applications no speed tap or airflow modifications should be made f...

Page 16: ...tened All panels must be in place and secured For Air Tight application gasket must be positioned at prescribed locations to achieve 1 4 leakage Tubing must be leak free Condensate line must be trappe...

Page 17: ...95 625 615 515 T9 995 970 925 910 860 850 800 790 730 T1 750 725 670 655 585 570 465 455 360 T2 920 895 845 830 780 770 710 700 615 T3 985 960 915 900 850 840 785 775 710 T4 1185 1165 1125 1115 1070 1...

Page 18: ...T2 1580 1550 1490 1470 1400 1390 1315 1305 1230 T3 1635 1610 1560 1545 1480 1470 1400 1390 1315 T4 1851 1810 1768 1733 1704 1662 1613 1486 1358 T5 1820 1795 1750 1735 1680 1670 1605 1595 1525 T6 1465...

Page 19: ...the connections between room thermostat and the air handlers and the connections between the air handlers and the Condensing Unit or Heat Pump with optional connections to Outdoor Thermostats For eac...

Page 20: ...UNIT 24V CONNECTION BL YL YL WH GR RD 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT AIR HANDLER Y G W W2 R COOLING UNIT WITH OPTIONAL HEAT KITS OF 15 kW AND ABOVE AND ROOM THERMOSTAT WITH TWO STAGES OF H...

Page 21: ...EMOVE WIRE WHEN USING OUTDOOR THERMOSTAT NOMENCLATURE OT OUTDOOR THERMOSTAT OPTIONAL EHR EMERGENCY HEAT RELAY OPTIONAL COLOR CODES RD RED YL YELLOW BL BLUE BR BROWN OR ORANGE WH WHITE G C R HEAT PUMP...

Page 22: ...PLUG CONNECTOR TRANSFORMER HIGH VOLTAGE LOW VOLTAGE HIGH VOLTAGE LOW VOLTAGE PLF 2 COLOR CODE TR 6 5 PLM 4 4 24V 5 1 2 3 EM WIRING CODE 208 240 VOLTS 1 1 PLF PLM L1 PLM 2 L2 IF REPLACEMENT OF THE ORI...

Page 23: ...AGE HIGH VOLTAGE LOW VOLTAGE PLF 2 COLOR CODE TR 6 5 PLM 4 4 24V 5 1 2 3 EM WIRING CODE 208 240 VOLTS 1 1 PLF PLM L1 PLM 2 L2 IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESS...

Page 24: ...am on the unit for the most up to date wiring 3 Phase Heat Kit 18 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILU...

Page 25: ...icals can cause premature aluminum evaporator coil failure Any cleaners that contain corrosive chemicals including but not limited to chlorine and hydroxides should not be used An alternate cleaning m...

Page 26: ...WB F DB F WB F Heating Supply Air Temperature DB F Temperature Rise DB F Delta T Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV an...

Page 27: ...27 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 28: ...REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional...

Reviews: