background image

Detail

code

Division

0

1

2

3

4

5

6

7

8

9

A

C

E

F

H

J

Indoor Unit

A

Malfunction of 
indoor unit PCB

Malfunction of 
freezing protection

Malfunction 
of electronic 
expansion valve

Malfunction 
of electronic 
expansion valve

C

Malfunction of liquid 
pipe thermistor for 
heat exchanger

Malfunction of gas 
pipe thermistor for 
heat exchanger

Outdoor Unit

E

Protection devices 
activated (unifi ed)

Defect of outdoor 
unit PCB

Missing of earth 
leakage detection 
core

Actuation of high 
pressure switch 
(HPS)

Actuation of low 
pressure switch 
(LPS)

Inverter compressor 
motor or overheat

STD compressor 
motor overcurrent/
lock

Malfunction of 
outdoor unit fan 
motor system

Overcurrent of 
inverter compressor

Malfunction 
of electronic 
expansion valve coil

F

Malfunction of 
discharge pipe 
temperature

Abnormal high 
pressure actuation 
of HPS

H

Malfunction of 
sensor system of 
compressor

Malfunction of room 
temperature sensor 
or humidifi er unit 
damper

Malfunction of 
power supply 
sensor

Malfunction of high 
pressure switch 
(HPS)

Malfunction of low 
pressure switch 
(LPS)

Malfunction of 
compressor motor 
overload thermistor

Malfunction of 
position detection 
sensor

Malfunction of 
outdoor unit fan 
motor signal

Malfunction of 
compressor input 
(CT) system

Malfunction 
of outdoor air 
thermistor

Malfunction of 
discharge air 
thermistor

Malfunction of  (hot) 
water temperature 
thermistor

J

Miswiring of 
thermistor

Malfunction of 
pressure sensor

Malfunction of 
current sensor of 
compressor

Malfunction of 
discharge pipe 
thermistor

Malfunction of low 
pressure equivalent 
saturated temperature 
sensor system

Malfunction of 
suction pipe 
thermistor

Malfunction of 
heat exchanger 
thermistor

Malfunction 
of thermistor 
(Refrigerant circuit)

Malfunction 
of thermistor 
(Refrigerant circuit)

Malfunction 
of thermistor 
(Refrigerant circuit)

Malfunction of high 
pressure sensor

Malfunction of low 
pressure sensor

L

Malfunction of 
inverter system

Malfunction of 
inverter PCB

El. compo. box 
temperature rise

Malfunction of 
inverter radiation fi n 
temperature rise

Inverter 
instantaneous 
overcurrent (DC 
output)

Inverter 
instantaneous 
overcurrent (AC 
output)

Total input 
overcurrent

Malfunction of 
overcurrent inverter 
compressor

Malfunction of 
inverter compressor 
startup error (Stall 
prevention)

Malfunction of 
power transistor

Malfunction of 
transmission 
between control 
and inverter PCB

P

Shortage of 
refrigerant amount  
(thermal storage 
unit)

Power voltage 
imbalance or 
inverter PCB

Automatic 
refrigerant charge 
operation stop

Reactor 
temperature 
abnormality

Malfunction of 
radiation fi n 
temperature sensor

Improper 
combination 
between inverter 
and fan driver

System

U

Shortage of 
refrigerant

Reverse phase, 
open phase

Malfunction of 
power supply or 
instantaneous 
power failure

Check operation 
not executed or 
transmission error

Malfunction of 
transmission 
between indoor and 
outdoor unit

Malfunction of 
transmission 
between indoor 
unit and remote 
controller

Malfunction of 
transmission 
between indoor 
units

Malfunction of 
transmission 
between outdoor 
units or outdoor 
storage unit

Malfunction of 
transmission 
between remote 
controllers

Malfunction of 
transmission (other 
system)

Improper 
combination of 
indoor and outdoor 
units

Malfunction 
of setting of 
centralized control 
equipment address

Malfunction of 
transmission 
between indoor 
unit and centralized 
control equipment

Malfunction of 
transmission 
(accessory device)

Others

7

System No. 2 
Compressor 
overheat

System No. 2 
Compressor 
overcurrent

System No. 2 
Fan motor 
overcurrent

System No. 2 
Actuation of high 
pressure switch 
(HPS)

System No. 2 
Actuation of low 
pressure switch 
(LPS)

System No. 2 
Malfunction of low 
pressure sensor

System No. 2 
Malfunction of high 
pressure sensor

System No. 1 
Malfunction of fan 
inter lock

System No. 2 
Malfunction of fan 
inter lock

System No. 2 
Malfunction of 
compressor current 
sensor

Malfunction of 
pump inter lock

8

Malfunction of 
entering water 
temperature 
thermistor

Malfunction of 
leaving water 
temperature 
thermistor or drain 
pipe heater

System No. 1 
Malfunction 
of refrigerant 
thermistor

System No. 2 
Malfunction 
of refrigerant 
thermistor

System No. 1 
Malfunction of 
heat exchanger 
thermistor

System No. 2 
Malfunction of 
heat exchanger 
thermistor

System No. 1 
Malfunction of 
discharge pipe 
thermistor

System No. 2 
Malfunction of 
discharge pipe 
temperature

Malfunction of 
brazed-plate heat 
exchanger freezing

Malfunction of 
dehumidifi cation 
or leaving water 
temperature 
thermistor

System No. 1 
Malfunction of 
suction pipe 
thermistor 1 for 
heating

System No. 1 
Malfunction of 
suction pipe 
thermistor 2 for 
heating

Abnormal hot water 
high temperature

9

Abnormal chilled 
water quantity or 
abnormal AXP

System No. 2 
Malfunction 
of electronic 
expansion valve

System No. 2 
Malfunction of 
suction pipe 
thermistor

System No. 1 
Malfunction of 
inverter system

System No. 2 
Malfunction of 
inverter system

Malfunction of 
thermal storage unit

Malfunction of 
thermal storage 
brine pump

Malfunction of 
thermal storage 
brine tank

System No. 2 
Malfunction of 
suction pipe 
thermistor 1 for 
heating

System No. 2 
Malfunction of 
suction pipe 
thermistor 2 for 
heating

Chiller

Detail

code

Division

0

1

2

3

4

5

6

7

8

9

A

C

E

F

H

J

Indoor Unit

A

Malfunction of drain 
level system

Malfunction of 
freezing protection

Malfunction of 
dust collector of air 
cleaner

C

Malfunction of liquid 
pipe thermistor for 
heat exchanger

Malfunction 
of suction air 
thermistor

Malfunction of 
thermostat sensor 
in remote controller

System

U

Reverse phase, 
open phase

Malfunction of 
power supply or 
instantaneous 
power failure

Check operation 
not executed or 
transmission error

Malfunction of 
transmission 
between indoor and 
outdoor unit

Malfunction of 
transmission 
between indoor 
unit and remote 
controller

Malfunction of 
transmission 
between indoor 
units

Malfunction of 
transmission 
between outdoor 
units or outdoor 
storage unit

Malfunction of 
transmission 
between remote 
controllers

Malfunction of 
transmission (other 
system)

Improper 
combination of 
indoor and outdoor 
units

Malfunction 
of setting of 
centralized control 
equipment address

Malfunction of 
transmission 
between indoor 
unit and centralized 
control equipment

M

Malfunction of 
central remote 
controller PCB

Malfunction of 
transmission between 
optional controllers for 
centralized control

Improper combination 
of optional controllers 
for centralized control

Address 
duplication, 
improper setting

Fan Coil

Summary of Contents for ARC447A

Page 1: ...ing operations 1 short beep Conduct steps 3 and 4 Continue the operation in step 4 until a buzzer remains ON The continuous buzzer indicates that the malfunction code is confirmed Continuous beep No a...

Page 2: ...button is not pressed for 1 minute The figure of the ten s place blinks Try again from the start when the figure does not blink Self Diagnosis by Remote Controller Residential Air conditioner TIMER CA...

Page 3: ...Malfunction of thermistor Refrigerant circuit Malfunction of thermistor Refrigerant circuit Malfunction of high pressure sensor Malfunction of low pressure sensor Malfunction of oil pressure sensor or...

Page 4: ...ollers Malfunction of transmission other system Improper combination of indoor and outdoor units Malfunction of setting of centralized control equipment address Malfunction of transmission between ind...

Page 5: ...ure thermistor in remote controller abnormality Defective room temperature thermistor in remote controller Defective remote controller PCB External factor Noise etc k k k k k Malfunction code Malfunct...

Page 6: ...nsor in mistake for low pressure sensor Defective low pressure sensor Defective outdoor unit PCB k k k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclai...

Page 7: ...k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclaim ventilator Chiller Fan Coil System U7 Malfunction of transmission between outdoor units or outdoor...

Page 8: ...n of heat exchanger thermistor Defective connector contact Defective heat exchanger thermistor k 86 System No 1 Malfunction of discharge pipe thermistor Defective connecting connector Defective discha...

Reviews: