Simple Self-Diagnosis by Malfunction Code

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

Indoor Unit

A0

External protection device 
activated

External protection device connected to the terminal strip 
T1-T2 of indoor unit is activated

k k k

A1

Malfunction of indoor unit PCB

Defective indoor unit PCB
External factor (Noise etc.)

k k k k k k

A3

Drain Level Control System 
Abnormality

Drain clogging, upward slope, etc.
Defective drain pump
Defective fl oat switch or short circuit connector

k k k

k

k

A4

Malfunction of freezing protection

Shortage of water volume
Low water temperature setting
Defective water temperature thermistor

k k k k

k k

A5

High pressure control in heating, 
freeze-up protection control in 
cooling

Clogged air fi lter of indoor unit and short circuit
Defect of indoor unit heat exchanger thermistor

k k k k

A6

Malfunction of fan motor

Broken wires in, short circuit of, or disconnection of 
connectors from the fan motor harness
Defective fan motor
Defective indoor unit PCB

k k k k k

A7

Malfunction of swing fl ap motor

Defective swing fl ap motor
Defective indoor unit PCB
Defective connection cable
Defective airfl ow direction adjusting fl ap-cam

k k

A8

Malfunction of power supply or AC 
input overcurrent

Defective power supply voltage
Defective connection on signal line
Defective wiring

k k

k

A9

Malfunction of electronic expansion 
valve

Defective electronic expansion valve coil
Defective indoor unit PCB
Defective relay cables

k k k k k

AA

Heater overheat

26WH is activated

k

k

AF

Malfunction of a humidifi er system

Humidifi er unit (optional accessory) leaking
Defective drain piping (upward slope, etc.)
Defective indoor unit PCB

k k

k

AH

Malfunction of dust collector of air 
cleaner

Defect of dust collecting element
Stained insulator part
Defect of high voltage power supply unit
Defect of indoor unit PCB

k k k

k

AJ

Malfunction of capacity setting 
(Indoor unit PCB)

The capacity setting adaptor was not installed when 
replacing PCB.
Defective indoor unit PCB

k k k

C1

Failure of transmission (between 
indoor unit PCB and sub PCB)

Defective connection of the connector between indoor 
unit PCB 

k k

C4

Malfunction of liquid pipe 
thermistor for heat exchanger

Defective thermistor for liquid pipe 
Defective indoor unit PCB
Defective connector contact

k k k k k k k

C5

Malfunction of gas pipe thermistor 
for heat exchanger

Defective thermistor for gas pipe
Defective indoor unit PCB
Defective connector contact

k

k k k k

C6

Malfunction of fan motor sensor or 
fan control driver

Defective fan PCB
Defective connection of capacity setting adaptor
Field setting error

k k

C7

Front panel driving motor fault

Defective front panel driving motor
Defective limit switch

k

C9

Malfunction of suction air 
thermistor

Defective thermistor for suction air
Defective indoor unit PCB
Defective connector contact

k k k k k

k

CA

Malfunction of discharge air 
thermistor

Defective thermistor for discharge air
Defective indoor unit PCB
Defective connector contact

k

k k k

CC

Malfunction of humidity sensor 
system

Defective humidity sensor
Defective connector contact

k k

k

CJ

Room temperature thermistor in 
remote controller abnormality

Defective room temperature thermistor in remote controller
Defective remote controller PCB
External factor (Noise etc.)

k k k k

k

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

Outdoor Unit

E0

Protection devices activated 
(unifi ed)

Protection device connected to outdoor unit PCB actuated
Defective protection device connector contact

k k

k

E1

Defective outdoor unit PCB

Defective outdoor unit PCB 
Defective connection of inside/ outside relay wires

k k k k

k

E3

Actuation of high pressure switch 
(HPS)

Dirty outdoor unit heat exchanger
Defective high pressure switch
Clogged refrigerant piping
Defective connector contact

k k k k

E3

System No.1
Actuation of high pressure switch 
(HPS)

Dirty outdoor unit heat exchanger
Shortage of water volume
Clogged refrigerant piping
Defective connector contact
Defective HPS

k

E4

Actuation of low pressure switch 
(LPS)

Abnormally drop in low pressure
Defective low pressure sensor
Defective outdoor unit PCB
Defective connector contact

k k k

k

E5

Inverter compressor motor or 
overheat

Inverter compressor lock
High differential pressure
Defective inverter PCB
UVW connection error
Defective connector contact

k k k k

k

E6

STD compressor motor 
overcurrent/lock

Defective compressor
Defective control PCB
The stop valve is not opened

k k k k

E6

System No.1 Compressor 
overcurrent

Defective electronic expansion valve
Shortage of refrigerant amount
Defective compressor

k

E7

Malfunction of outdoor unit fan 
motor system

Fan motor failure
Neglect to connect or defective connection of harness/
connector between the fan motor and the PCB
Fan does not rotate due to foreign matters caught in it

k k k k

k

E8

Overcurrent of inverter compressor

Defective compressor
Defective inverter main circuit capacitor 
Defect of outdoor unit PCB
Defect of power transistor

k

k

E9

Malfunction of electronic expansion 
valve coil

Disconnection of connectors from electronic expansion valves
Defective electronic expansion valve coil
Defective outdoor unit control PCB

k k k

k

EA

Malfunction of four way valve or 
cool/heat switchin

Defective four way valve
Shortage of gas
Defective outdoor unit PCB
Defective thermistor

k

EC

Malfunction of entering water 
temperature

Cooling water temperature abnormality
Defective outdoor unit PCB
Defective thermistor

k

F3

Malfunction of discharge pipe 
temperature

Defective discharge pipe thermistor
Abnormal discharge pipe temperature
Defective outdoor unit control PCB
Defective connector contact

k k k k

k

F6

Abnormal high pressure or 
refrigerant overcharged

Refrigerant overcharged
Disconnection of heat exchanger deicer thermistor
Disconnection of outdoor air thermistor
Disconnection of liquid pipe temperature thermistor
Defective outdoor unit PCB

k k k k

H0

Malfunction of sensor system of 
compressor

Harness is disconnected, or defective connection
Defective PCB

k

k

H1

Malfunction of room temperature 
sensor or humidifi er unit damper

Defective limit switch
Defective damper

k

k

H3

Malfunction of high pressure switch 
(HPS)

Defective high pressure switch
Broken wire
Defective outdoor unit PCB
Defective connector contact

k k k k

k

H4

Malfunction of low pressure switch 
(LPS)

Defective low pressure switch
Broken wire
Defective outdoor unit PCB
Defective connector contact

k k

k

Summary of Contents for ARC447A

Page 1: ...ing operations 1 short beep Conduct steps 3 and 4 Continue the operation in step 4 until a buzzer remains ON The continuous buzzer indicates that the malfunction code is confirmed Continuous beep No a...

Page 2: ...button is not pressed for 1 minute The figure of the ten s place blinks Try again from the start when the figure does not blink Self Diagnosis by Remote Controller Residential Air conditioner TIMER CA...

Page 3: ...Malfunction of thermistor Refrigerant circuit Malfunction of thermistor Refrigerant circuit Malfunction of high pressure sensor Malfunction of low pressure sensor Malfunction of oil pressure sensor or...

Page 4: ...ollers Malfunction of transmission other system Improper combination of indoor and outdoor units Malfunction of setting of centralized control equipment address Malfunction of transmission between ind...

Page 5: ...ure thermistor in remote controller abnormality Defective room temperature thermistor in remote controller Defective remote controller PCB External factor Noise etc k k k k k Malfunction code Malfunct...

Page 6: ...nsor in mistake for low pressure sensor Defective low pressure sensor Defective outdoor unit PCB k k k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclai...

Page 7: ...k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclaim ventilator Chiller Fan Coil System U7 Malfunction of transmission between outdoor units or outdoor...

Page 8: ...n of heat exchanger thermistor Defective connector contact Defective heat exchanger thermistor k 86 System No 1 Malfunction of discharge pipe thermistor Defective connecting connector Defective discha...