Simple Self-Diagnosis by Malfunction Code

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

Outdoor Unit

P2

Automatic refrigerant charge 
operation stop

The stop valve is not opened
Closed valve of refrigerant tank

k k k

k

P3

Malfunction of thermistor in switch 
box

Defective connection of thermistor
Defective reactor thermistor
Defective inverter PCB

k k k k

k

P4

Malfunction of radiation fi n 
temperature sensor

Defective radiation fi n temperature thermistor
Defective inverter PCB
Defective INV. compressor
Defective fan motor

k k k k

k

P8

Heat exchanger freezing protection 
during automatic refrigerant 
charging

(Close the refrigerant cylinder. Start again from step 1.)

k k k

P9

Malfunction of fan motor 
(humidifi er unit)

Defective fan motor
Defective outdoor unit PCB
Broken relay harness
Defective connector contact

k

P9

Automatic refrigerant charge 
operation completed

k k k k

PA

Refrigerant cylinder during 
automatic refrigerant charging

Refrigerant cylinder of master unit is empty

k k k

PA

Broken wire of heater 
(humidifi er unit)

Defective heater unit
Defective thermistor
Defective outdoor unit PCB

k

PC

Refrigerant cylinder during 
automatic refrigerant charging

Refrigerant cylinder of slave unit 2 is empty

k k

PE

Automatic refrigerant charge 
operation nearly completed

k k k

PH

Refrigerant cylinder during 
automatic refrigerant charging

Defective heater unit
Defective connector contact
Defective thermistor
Defective outdoor unit PCB

k

k k

PJ

Malfunction of capacity setting 
(Outdoor unit PCB)

Capacity setting adaptor is not installed
Improper capacity setting adaptor
Defective outdoor unit PCB

k

PJ

Improper combination between 
inverter and fan driver

Mis-matching of type of PCB
Improper (or no) fi eld setting after replacing outdoor unit 
main PCB

k k k

k

System

U0

Shortage of refrigeran

Refrigerant shortage and refrigerant clogging (wrong 
piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB

k k k k

k

U1

Reverse phase, open phase

Power supply reverse phase
T phase open phase
Defective outdoor unit PCB (A1P)

k k k k k k k

U2

Malfunction of power supply or 
instantaneous power failure

Abnormal power supply voltage
Instantaneous power failure
Defective main circuit wiring

k k k k

k k

U3

Check operation not executed or 
transmission error

Check operation is not executed.

k k k k k k k

U4

Malfunction of transmission 
between indoor and outdoor unit

Short circuit in indoor-outdoor or outdoor-outdoor 
transmission wiring (F1 / F2), or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor unit PCB

k k k k k k k

U5

Malfunction of transmission 
between indoor unit and remote 
controller

Transmission error between indoor unit and remote 
controller
Connection of 2 main remote controllers (when using 2 
remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Transmission error caused by noise

k k k k

k k

U6

Malfunction of transmission 
between indoor units

Faulty wiring 
External factor (Noise etc.)
Defective indoor unit PCB

k k

k k

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

System

U7

Malfunction of transmission 
between outdoor units or outdoor 
storage unit

Connection error of transmission wirings between outdoor 
unit and external control adaptor for outdoor unit
Connection error of transmission wirings between outdoor 
units
Defective outdoor unit PCB

k

k k

k k

U8

Malfunction of transmission 
between remote controllers

Transmission error between main and sub remote 
controller
Connection between sub remote controllers
Defective remote controller PCB

k k k k k k

U9

Malfunction of transmission (other 
system)

Transmission error between other indoor and outdoor units
Defective electronic expansion valve of other indoor unit
Defective indoor unit PCB of other indoor unit
Improper connection of transmission wiring between 
indoor and outdoor unit

k k k

k k

UA

Defect of indoor/outdoor power 
supply

Wrong model connections
Improper power supply
Wrong PCB connected
Defective PCB

k

UA

Improper combination of indoor 
and outdoor units

Excess of connected indoor units
Defective outdoor unit PCB
Mismatch of the refrigerant type of indoor and outdoor unit
Setting of outdoor unit PCB was not carried out after 
replacing to spare PCB

k k k

k

UA

Remote temperature setting wire 
disconnection

Remote temperature setting wire disconnection
Defective connector contact

k

UC

Malfunction of setting of centralized 
control equipment address

Address duplication of centralized control equipment
Defective indoor unit PCB

k k k k k k

UE

Malfunction of transmission 
between indoor unit and 
centralized control equipment

Transmission error between optional controllers for 
centralized control equipment and indoor unit
Connector for setting main controller is disconnected.(or 
disconnection of connector for independent / combined 
use changeover switch.)
Defective PCB for central remote controller
Defective indoor unit PCB

k k k k k k

UF

System is not set yet

Improper connection of transmission wiring between 
indoor-outdoor units and outdoor-outdoor units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened

k k k k

UH

Malfunction of system

Improper connection of transmission wiring between 
indoor-outdoor units and outdoor-outdoor units
Defective indoor unit PCB
Defective outdoor unit PCB 

k

k k

UJ

Malfunction of transmission 
(accessory device)

Defect of accessory devices
Faulty wiring

k k k k

k

Other

s

60

External protection device 
activated (Heat reclaim ventilator)

Actuation of external protection device
Defective output signal wiring 
Defective control PCB

k

64

Malfunction of indoor air thermistor  
(Heat reclaim ventilator)

Defective connector contact
Defective  indoor air thermistor
Defective control PCB

k

65

Malfunction of outdoor air 
thermistor (Heat reclaim ventilator)

Defective connector contact
Defective outdoor air thermistor
Defective control PCB

k

6A

Malfunction of damper system 
(Heat reclaim ventilator)

Defective connector contact
Defective limit switch
Defective damper motor
Defective control PCB

k

70

System No. 2
Compressor overheat

Shortage of refrigerant amount 
Defective connector contact
Leakage of four way valve

k

71

System No. 2
Compressor overcurrent

Shortage of refrigerant amount
Short circuit
Defective compressor

k

Summary of Contents for ARC447A

Page 1: ...ing operations 1 short beep Conduct steps 3 and 4 Continue the operation in step 4 until a buzzer remains ON The continuous buzzer indicates that the malfunction code is confirmed Continuous beep No a...

Page 2: ...button is not pressed for 1 minute The figure of the ten s place blinks Try again from the start when the figure does not blink Self Diagnosis by Remote Controller Residential Air conditioner TIMER CA...

Page 3: ...Malfunction of thermistor Refrigerant circuit Malfunction of thermistor Refrigerant circuit Malfunction of high pressure sensor Malfunction of low pressure sensor Malfunction of oil pressure sensor or...

Page 4: ...ollers Malfunction of transmission other system Improper combination of indoor and outdoor units Malfunction of setting of centralized control equipment address Malfunction of transmission between ind...

Page 5: ...ure thermistor in remote controller abnormality Defective room temperature thermistor in remote controller Defective remote controller PCB External factor Noise etc k k k k k Malfunction code Malfunct...

Page 6: ...nsor in mistake for low pressure sensor Defective low pressure sensor Defective outdoor unit PCB k k k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclai...

Page 7: ...k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclaim ventilator Chiller Fan Coil System U7 Malfunction of transmission between outdoor units or outdoor...

Page 8: ...n of heat exchanger thermistor Defective connector contact Defective heat exchanger thermistor k 86 System No 1 Malfunction of discharge pipe thermistor Defective connecting connector Defective discha...

Reviews: