Simple Self-Diagnosis by Malfunction Code

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

Other

s

72

System No. 2
Fan motor overcurrent

Defective fan motor connector contact
Defective fan motor 
Defective PCB

k

73

System No. 2
Actuation of high pressure switch 
(HPS)

Dirty heat exchanger
Shortage of water volume
Clogged refrigerant piping
Defective connector contact
Defective HPS

k

74

System No. 2
Actuation of low pressure switch 
(LPS)

Clogged refrigerant piping
Defective connector contact
Shortage of gas
Defective LPS

k

75

System No. 2
Malfunction of low pressure sensor

Defective connector contact
Defective low pressure sensor
Defective PCB

k

76

System No. 2
Malfunction of high pressure 
sensor

Defective connector contact
Defective high pressure sensor
Defective PCB

k

77

System No. 1
Malfunction of fan inter lock

Defective relay contact
Broken wire

k

78

System No. 2
Malfunction of fan inter lock

Defective relay contact
Broken wire

k

7A

System No. 2
Malfunction of compressor current 
sensor

Defective current sensor
Defective compressor
Defective outdoor unit PCB

k

7C

System No. 2
Malfunction of pump inter lock

Cooling water pump interlock actuated

k

80

Malfunction of entering water 
temperature thermistor

Defective connector contact
Defective entering water temperature thermistor

k

81

Malfunction of leaving water 
temperature thermistor or drain 
pipe heater

Defective connector contact
Defective leaving water temperature thermistor

k

82

System No. 1
Malfunction of refrigerant 
thermistor

Defective connector contact
Defective refrigerant thermistor

k

83

System No. 2
Malfunction of refrigerant 
thermistor

Defective connector contact
Defective refrigerant thermistor

k

84

System No. 1
Malfunction of heat exchanger 
thermistor

Defective connector contact
Defective heat exchanger thermistor

k

85

System No. 2
Malfunction of heat exchanger 
thermistor

Defective connector contact
Defective heat exchanger thermistor

k

86

System No. 1 
Malfunction of discharge pipe 
thermistor

Defective connecting connector
Defective discharge pipe thermistor

k

88

System No. 2
Malfunction of discharge pipe 
temperature

Shortage of gas 
Defective discharge pipe thermistor
Defective connector contact
Clogged refrigerant piping

k

89

Malfunction of brazed-plate heat 
exchanger freezing

Dirty heat exchanger
Shortage of refrigerant amount
Defective thermistor

k

8A

System No. 2
Malfunction of leaving water 
temperature thermistor

Defective connector contact
Defective leaving water temperature thermistor

k

8E

System No. 1
Malfunction of suction pipe 
thermistor 1 for heating

Defective connector contact
Defective suction pipe thermistor

k

8F

System No. 1
Malfunction of suction pipe 
thermistor 2 for heating

Defective connector contact
Defective suction pipe thermistor

k

Malfunction 

code

Malfunction Contents

Supposed causes

Objects

RA

SkyAir

VR

V

Pa

c

k

a

g

e

Heat rec

laim ventilator

Chiller

F

an Coil

Other

s

8H

Abnormal hot water high 
temperature

Three way valve malfunction
Defective thermistor
Defect of water temperature setting

k

90

Abnormal chilled water quantity or 
abnormal AXP

Shortage of water volume
Disconnection of AXP

k

91

System No. 2
Malfunction of electronic expansion 
valve

Defective connector contact
Defective electronic expansion valve coil

k

92

System No. 2
Malfunction of suction pipe 
thermistor

Defective connector contact
Defective suction pipe thermistor

k

94

Malfunction of transmission 
(between heat reclaim ventilator 
and fan unit)

Defective fan unit PCB
Defective connecting wire between (1) and (2)

k

95

System No. 1
Malfunction of inverter system

Defective fan inverter unit

k

96

System No. 2
Malfunction of inverter system

Defective fan inverter unit

k

97

Malfunction of thermal storage unit

Defective thermal storage unit

k

98

Malfunction of thermal storage 
brine pump

Actuation of thermal storage brine pump overcurrent (OC)

k

99

Malfunction of thermal storage 
brine tank

Low water level of thermal storage brine tank

k

Summary of Contents for ARC447A

Page 1: ...ing operations 1 short beep Conduct steps 3 and 4 Continue the operation in step 4 until a buzzer remains ON The continuous buzzer indicates that the malfunction code is confirmed Continuous beep No a...

Page 2: ...button is not pressed for 1 minute The figure of the ten s place blinks Try again from the start when the figure does not blink Self Diagnosis by Remote Controller Residential Air conditioner TIMER CA...

Page 3: ...Malfunction of thermistor Refrigerant circuit Malfunction of thermistor Refrigerant circuit Malfunction of high pressure sensor Malfunction of low pressure sensor Malfunction of oil pressure sensor or...

Page 4: ...ollers Malfunction of transmission other system Improper combination of indoor and outdoor units Malfunction of setting of centralized control equipment address Malfunction of transmission between ind...

Page 5: ...ure thermistor in remote controller abnormality Defective room temperature thermistor in remote controller Defective remote controller PCB External factor Noise etc k k k k k Malfunction code Malfunct...

Page 6: ...nsor in mistake for low pressure sensor Defective low pressure sensor Defective outdoor unit PCB k k k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclai...

Page 7: ...k k Malfunction code Malfunction Contents Supposed causes Objects RA SkyAir VRV Package Heat reclaim ventilator Chiller Fan Coil System U7 Malfunction of transmission between outdoor units or outdoor...

Page 8: ...n of heat exchanger thermistor Defective connector contact Defective heat exchanger thermistor k 86 System No 1 Malfunction of discharge pipe thermistor Defective connecting connector Defective discha...

Reviews: