Troubleshooting
SiBE04-401
112
Service Diagnosis
4.15
DC Voltage / Current Sensor Abnormality
Remote
Controller
Display
H8
Method of
Malfunction
Detection
Detecting abnormality of the DC sensor by the running frequency of compressor and by the
input current multiplied DC voltage and current.
Malfunction
Decision
Conditions
The compressor running frequency is below 52 Hz.
(The input current is also below 0.5 A.)
If this error repeats 4 times, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Outdoor unit PCB defective
Troubleshooting
Replace the outdoor unit PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for ARKH20CVMB9
Page 67: ...Control Specification SiBE04 401 58 Function and Control ...
Page 97: ...Instruction SiBE04 401 88 System Configuration ...
Page 141: ...Check SiBE04 401 132 Service Diagnosis ...
Page 211: ...Outdoor Unit RK X H C ARK X H C R Y N C SiBE04 401 202 Removal Procedure ...
Page 215: ...Others SiBE04 401 206 Others ...