IM 817-4
Page 11 of 60
Notes:
1. Horizontal blade wall louver shown. Vertical blade wall louver also
available with Ventimatic shutter.
2. Optional exterior grille matches unit ventilator wall louver in material
and design. Mounted on wall louvers.
3. Optional steel interior wall grille should be used to conceal the interior
wall opening whenever the Ventimatic shutter is not located behind
shelf cabinets or DraftStop enclosure. Hardware to mount the interior
wall grille is not included.
Installing the VentiMatic Shutter Assembly
The VentiMatic Shutter Assembly is mounted on an installed wall
louver. For larger units with 100% ventilation air dampers, two
VentiMatic Shutters may be mounted side by side on the same louver.
See figure 24.
The size and appearance of the wall louvers with or without optional
grilles used with the unit ventilator, and the VentiMatic Shutter, are
identical.
When installing VentiMatic Shutter(s) on the wall louver, make sure
all moving parts are free to operate unobstructed and placed level
and plumb for proper operation. If optional steel interior wall grille is
furnished, install as shown in Figure 22.
Figure 19 - Suggested method for fastening louver (without flange)
inside wall opening .
Figure 22 - Louver , VentiMatic Shutter, Interior Wall Grille Details,
Dimensions
As Directed
By Architect
3
⁄
4
" (19mm) Approx.
7"
(178mm)
Cement Mortar
Steel Interior Wall Grille
(Optional) See Note 3
12
5
⁄
8
"
(314mm)
3
⁄
4
" (19mm) Approx.
Bird
Screen
Do Not Block Drain
Holes With Caulk or
Mortar
Not
Less
Than 9"
(229mm)
Cement Mortar
C
(see table 3, page 10)
Wall Opening
Louver
(Bird Screen Not Shown)
Angle Iron
(by others)
Room Side
Exterior
Caulk
(top and 2 Sides)
Louvers
Drain Holes
(Do Not Block)
Flange
(4 Sides)
1" Minimum
Lintels (By Others)
Bird Screen
Sealed Cement Mortar
Pitched Away from Unit
Toward Louver
Figure 20 - Vertical or Horizontal Blade Wall Intake Louver (Flanged)
(Vertical Blade Shown)
Drain Holes
(Do Not Block
With Mortar
or Caulking
Materials
Bird Screen
Sealed Cement
Mortar Pitched
Away from Unit
Toward Louver
1" Minimum
Figure 21 - Vertical or Horizontal Blade Wall Intake Louver (Recessed
Without Flange) (Horizontal Blade Shown)
Lintels (By Others)
Louvers
Aluminum Wall Louver
Assembly With Bird Screen
(See Note 1)
B
(see table 3,
page 10)
Steel
VentiMatic
Shutter
Assembly
4
1
⁄
8
"
(105mm)
23
7
⁄
8
" (606mm)
or
35
7
⁄
8
" (911mm)
2" (51mm)
10
3
⁄
8
"
(264mm)
3" (76mm)
Decorative Exterior Grille Also Available (See Note 2, above)
(Bird Screen not shown)
Figure 23 - Single VentiMatic Shutter & Wall Louver
Outside