IM 817-7
56 www.DaikinApplied.com
Digital Ready Unit Electrical
Connections
WARNING
Rigorously adhere to field wiring procedures regarding proper
lockout and tagout of components.
WARNING
To avoid electrical shock, personal injury or death:
1. Installer must be qualified, experienced technician.
2. Disconnect power supply before installation to prevent
electrical shock and damage to equipment.
3. Make all connections in accordance with electrical wiring
diagrams, and in compliance with national and local codes.
Use copper conductors only.
4. Do not exceed ratings of the device. This is a low voltage
device: Never apply more than 12VAC/VDC to any lead or
damage will result.
5. Avoid locations where excessive moisture, corrosive fumes,
or vibrations are present.
, and refer to Digital Ready component
details
and the job-specific electrical
drawings before proceeding with field power and control
wiring. See also the wiring diagram provided on the unit
ventilator right front access panel.
In addition, those unit ventilators equipped with optional
electric heating coil have electric heating coil power
connections at right end only.
Procedure
1 .
Provide power supply to right end compartment to
match unit nameplate.
CAUTION
Use copper conductors only. Use of aluminum conductors may
result in equipment failure and overheating hazards. All wiring in
right hand compartment must be class 1.
2 .
Wire leads provided from unit ventilator electric
connection box to load side of unit power switch
(switch provided by Daikin). The junction box has
1"(25mm) and 2"(51mm) knockouts, located 10-
1/2"(267mm) from right end of unit.
3 .
Provide ground wire from grounding screw in switch
junction box to switch ground terminal.
4 .
Wire field power supply to line side of unit power
switch. Wire ground conductor to switch ground
terminal.
5 .
Mount unit power switch in switch junction box and
install switch cover plate (provided).
6 .
(
A
) shows switch
location for valve control units and (
B
), (
C
) and (
D
)
show location for Face & Bypass control units. (
B
) is
for 208, 230 and 265 volt units.
7 .
for terminal strip designations.
Table 40: Floor AV Electrical Data/Motor Data and Unit
Amp without electric heat
Unit
Series
CFM
(Nom .)
L/s
Motor
HP
Watts
Unit Current #
115V
208V
230V
265V
S07
750
354
1/4
164
1.8
1.0
0.9
0.8
S10
1000
472
1/4
244
3.1
1.7
1.5
1.3
S13
1250
590
1/4
306
3.5
1.9
1.8
1.5
S15
1500
708
1/4
334
3.7
2.0
1.8
1.6
#
Amps at unit voltage, 60 Hz, single phase
Figure 115: Unit Left End Compartment and Terminal Strip
Terminal Strip
Left End Compartment
for Mounting Controls
by Others
Figure 116: Terminal Strip