CAUTION
Turn off unit before servicing to avoid danger of injury from
rotating fans.
Turn off the unit, (fan speed switch or unit on/off switch
is located behind the right front end compartment panel).
Remove the center front panel, pull out the filter and
replace with a clean filter. Replace the center panel and
restart the unit.
Filters should be replaced during the first week of
placing into service to prevent dirt carry-over into the
internals of the unit and back into the classroom, (see
). A periodic filter changeout program should
be established. Filters should be checked monthly or
more often if conditions indicate. Filters are included
in all units. Daikin single-use filters are standard on
all but electric heat units, which come with permanent
wire mesh filters. Permanent wire mesh and renewable
media filters are available for non-electric heat units, in
lieu of single-use filters.
•
Single-use filters feature Amerglas media. They are
designed to be used once and discarded.
•
Permanent filters are metal filters that may be
removed for cleaning and reused numerous times.
•
Renewable media filters (
) consist of a
heavy painted metal structural frame and renewable
Amerglas media.
CAUTION
Electric heat units should ONLY use permanent wire mesh
filters.
Filters other than wire mesh are not intended for electric heat
units, and can cause unit damage, property damage or personal
injury.
CAUTION
Units must have a filter installed when operating. Operation
without a filter can compromise unit performance due to build up
of dust and dirt on components.
CAUTION
Dirty or clogged filters can impact unit performance, resulting in
damage to the unit.
Figure 135: Filter installation
12" Left Front
Access Panel
Motor
12" Right Front Access Panel
Top Access
Doors
Filter
Renewable Media (Single-use and
Permanent Wire Mesh Filters Also Available)
Structural
Frame
Complete Check, Test and
Start Procedure
(Included in the shipping envelope in the end compartment
of the unit). Provide completed Check, Test and Start
procedure to local Daikin representative and to specifying
engineer to verify proper start-up was completed.
Installer/Owner’s Responsibility
Protect your investment - read carefully
Your Daikin express written limited warranty does not cover
equipment failures that are caused by misuse, abuse, mis-
installation, failure to maintain the unit, etc. So, for example,
the following damage is not covered by warranty:
1 .
Progressive damage to machine from failure to check
and test at start-up.
2 .
Damage resulting from handling during installation or
damage resulting from transportation.
3 .
Incorrect or fluctuating power supply.
4 .
Damage resulting from failure to keep evaporator coil
and intake clean.
5 .
Damage resulting from freezing water or condensate,
inadequate or interrupted water supply, use of corrosive
water, rearrangement of unit piping system, fouling or
restriction of the water circuit by foreign material.
6 .
Inaccessibility of unit for service or parts installation
that prevents proper equipment operation.
7 .
Damage resulting from the use of the unit in a corrosive
atmosphere, ie., cleaning materials, fumes, etc
8 .
Damage caused by not cleaning or replacing filters.
9 .
Damage caused by accident, alteration of unit design,
or tampering.
Please complete and return the
“Check, Test and Start
Form beginning on page 74
immediately to protect
your warranty.