Specifications
Si12-714
24
Specifications
50Hz 220-230-240V / 60Hz 220-230V
Note:
1. The data are based on the conditions shown in the table below.
Model
4MKD100DVM
Cooling Capacity
kW
—
Power Consumption
W
—
Running Current
A
—
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Model
2YC63YXD#D
Motor Output
W
1,920
Refrigerant Oil
Model
SE56P
Charge
L
0.75
Refrigerant
Type
R-22
Charge
kg
3.0
Air Flow Rates
m³/min
H
62.7
L
60.8
cfm
H
2,214
L
2,147
Fan
Type
Propeller
Motor Output
W
70
Running Current
A
H: 0.67 / L: 0.65
Power Consumption
W
H: 107 / L: 99
Starting Current
A
15.9
Dimensions (H×W×D)
mm
770×900×320
Packaged Dimensions (H×W×D)
mm
900×925×390
Weight
kg
68
Gross Weight
kg
75
Operation Sound
dBA
54
Piping Connection
Liquid
mm
φ
6.4×2,
φ
9.5×2
Gas
mm
φ
12.7×2,
φ
15.9×2
Drain
mm
φ
25.0
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
Max. Piping Length
m
70 (for Total of Each Room)
m
25 (for One Room)
Amount of Additional Charge
g/m
Chargeless
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
m
7.5 (between Indoor Units)
Drawing No.
3D050028#1
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
7.5m