Troubleshooting
Si12-714
178
Service Diagnosis
5.2
Outdoor Units
4
: ON,
1
: OFF,
5
: Blinks
Green : Flashes when in normal condition
Red : OFF in normal condition
- : Not used for troubleshooting
∗
: Varies depending on the cases.
Note:
1. The indications in the parenthesis ( ) in the remote controller display column are displayed
only when system-down occurs.
2. When a sensor error occurs, check the remote controller display to determine which sensor
is malfunctioning.
If the remote controller does not indicate the error type, conduct the following operation.
*Turn the power switch off and back on again. If the same LED indication appears again
immediately after the power is turned on, the fault is in the thermistor.
*If the above condition does not result, the fault is in the CT.
3. The indoor unit error indication may take the precedence in the remote controller display.
Outdoor Unit LED Indication
Indication on
the remote
controller
Description of The Fault
Reference
Page
Green
Red
A
1
2
3
4
5
3
3
3
3
00
Outdoor unit in normal condition
(Conduct a diagnosis of the indoor unit.)
—
UA
Unspecified voltage (between indoor and outdoor units)
UH
Anti-icing function in other rooms
5
3
3
4
4
(
U0
)
Insufficient gas
5
4
3
3
4
U2
Low-voltage detection
5
4
3
4
4
A5
Freeze-up protection control
5
4
3
4
3
(
E5
)
OL activation (compressor overload)
5
3
4
4
3
(
E6
)
Compressor lock
5
4
4
4
4
E7
DC fan lock
5
3
4
3
4
E8
Input over current detection
5
4
3
3
3
EA
Four way valve abnormality
5
4
3
4
3
F3
Discharge pipe temperature control
5
4
3
4
4
F6
High pressure control in cooling
5
4
4
3
3
H6
Position sensor abnormality
H9
Outdoor air thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Heat exchanger thermistor or related abnormality
J8
Liquid pipe thermistor or related abnormality
J9
Gas pipe thermistor or related abnormality
P4
Radiation fin thermistor or related abnormality
5
4
4
3
3
H8
CT or related abnormality
5
4
4
3
4
L3
Electrical box temperature rise
5
3
3
3
4
L4
Radiation fin temperature rise
(Protection of driver overheating)
5
3
3
4
3
L5
Output over current detection