Field Setting for SkyAir Indoor Unit
SiENBE18-621
138
Test Operation
4.2.2 Infrared Remote Control
Note:
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual (optional hand book) for each optional accessory.
Procedure
1. When in the normal mode, push the “
” button for a minimum of four seconds,
and the FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “
” button.
3. Push the “
” button and select the FIRST CODE NO.
4. Push the “
” button and select the SECOND CODE NO.
5. Push the “
” button and the present settings are SET.
6. Push the “
” button to return to the NORMAL MODE.
4.3
Initial Setting Contents
MODE NO.
FIELD
S
ET MODE
S
ECOND CODE NO.
FIR
S
T CODE NO.
Setting Contents
Indoor Models
Filter
Sign
Filter Sign
Estimation of
Accumulated
Operating
Hours
High Air
Outlet
Velocity
(for
Application
to Ceiling
Higher
than 2.7m)
Selection
of Air
Flow
Direction
F, T, W
Air Flow
Direction
Adjust
Air Flow
Direction
Range
Setting
External
Static
Pressure
Long
Life
Filter
Type
Fan
Speed
Up
Simul-
taneous
operation
(Twin)
Ceiling
Suspended
type (FHQ)
(Heat
Pump)
FHQ
35~60
BUV1B
#
#
#
Ceiling
Mounted
Cassette
type
(FFQ)
(Heat
Pump)
FFQ
25~60
BV1B
#
#
#
#
#
#
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...