Test Operation and Field Setting for RA Indoor Unit
Test Operation
147
5.2
Jumper Settings
5.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two infrared remote controls can be set for
different addresses.
How to set the different addresses
"
Control PCB of the indoor unit
(1) Remove the electrical box.
(2) Cut the address jumper JA on the control PCB.
"
infrared remote control
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
5.2.2 Jumper Setting
(R4417)
ADDRE
SS
JA
ADDRE
SS
JA
EXI
S
T
1
CUT
2
ADDRE
SS
J4
EXI
S
T
CUT
1
2
J4
(R441
8
)
Jumper
(On indoor PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto start
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
Fan speed setting ;
Remote control
setting
Fan rpm is set to “0”
<Fan stop>
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...