225
Fault diagnosis by remote control
In the ARC433A series, the temperature display sections on the main unit indicate corresponding codes.
1. When the TIMER CANCEL button is held down for 5 seconds, a “
00
” indication flashes on the temperature
display section.
2. Press the TIMER CANCEL button repeatedly until a continuous beep is produced.
•
The code indication changes as shown below, and notifies with a long beep.
NOTE
Fault diagnosis
CODE
MEANING
SYSTEM
00
NORMAL
U0
REFRIGERANT SHOTAGE
U2
DROP VOLTAGE OR MAIN CIRCUIT OVERVOLTAGE
U4
FAILURE OF TRANSMISSION (BETWEEN INDOOR UNIT AND
OUTDOOR UNIT)
INDOOR UNIT
A1
INDOOR PCB DEFECTIVENESS
A5
HIGH PRESSURE CONTROL OR FREEZE-UP PROTECTOR
A6
FAN MOTOR FAULT
C4
FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
C9
FAULTY SUCTION AIR TEMPERATURE SENSOR
OUTDOOR UNIT
EA
COOLING-HEATING SWITCHING ERROR
E5
OL STARTED
E6
FAULTY COMPRESSOR START UP
E7
DC FAN MOTOR FAULT
E8
OPERATION HALT DUE TO DETECTION OF INPUT OVER CURRENT
F3
HIGH TEMPERATURE DISCHARGE PIPE CONTROL
F6
HIGH PRESSURE CONTROL (IN COOLING)
H6
OPERATION HALT DUE TO FAULTY POSITION DETECTION SENSOR
H8
CT ABNORMALITY
H9
FAULTY SUCTION AIR TEMPERATURE SENSOR
J3
FAULTY DISCHARGE PIPE TEMPERATURE SENSOR
J6
FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
L4
HIGH TEMPERATURE AT INVERTER CIRCUIT HEATSINK
L5
OUTPUT OVERCURRENT
P4
FAULTY INVERTER CIRCUIT HEATSINK TEMPERATURE SENSOR
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the TIMER CANCEL button down for 5 seconds. The code display also cancel
itself if the button is not pressed for 1 minute.
C
O N
TEMP
ON/OFF
POWERFUL
HOME LEAVE
MODE
TIMER
FAN
S
WING
S
ILENT
S
EN
S
OR
ON
CANCEL
OFF
TIMER CANCEL button
It c
a
ncel
s
the timer
s
etting.
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...