Troubleshooting for RA Indoor Unit
SiENBE18-621
274
Troubleshooting
4.3.2 DC Motor (Wall 20~35 D series and 50~71 class, Floor)
Remote Control
Display
A6
Method of
Malfunction
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Decision
Conditions
When the detected rotation speed is less than 50% of the H tap under maximum fan motor
rotation demand.
Supposed
Causes
"
Operation halt due to short circuit inside the fan motor winding.
"
Operation halt due to breaking of wire inside the fan motor.
"
Operation halt due to breaking of the fan motor lead wires.
"
Operation halt due to faulty capacitor of the fan motor.
"
Detection error due to faulty indoor unit PCB (1).