Troubleshooting for SkyAir Indoor Unit
SiENBE18-621
282
Troubleshooting
5.2
Malfunction of Drain Water Level System (Float Type)
Remote Control
Display
A3
Applicable
Models
FFQ-B & FHQ-BU
Method of
Malfunction
Detection
By float switch OFF detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
"
Failure of drain pump
"
Improper drain piping work
"
Drain piping clogging
"
Failure of float switch
"
Failure of indoor unit PCB
"
Failure of short-circuit connector