Troubleshooting for SkyAir Indoor Unit
SiENBE18-621
288
Troubleshooting
5.6
Swing Flap Motor Malfunction / Lock
Remote Control
Display
A7
Applicable
Models
FHQ-BU
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
"
Failure of motor
"
Failure of microswitch
"
Failure of connector connection
"
Failure of indoor unit PCB