Check
SiENBE18-621
354
Troubleshooting
Check No. 03
Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
Measurement point
Judgment
1 - 4
1M
Ω
or more
2 - 4
100k
Ω
or more
3 - 4
100
Ω
or more
4 - 7
100k
Ω
or more
GND
1 White
2 Or
a
nge
3
Brown
4 Bl
u
e
5
6
7 Red
(
S