Basic Control
Function
63
Δ
D Control
Receiving the capacity request signal from the indoor unit, the outdoor unit corrects its target
pressure for capacity control.
Controls
Δ
D signal from indoor unit as follows.
UP control :
When the UP command come from more than one indoor unit among
thermostat-ON indoor units.
Down control: When the down command come from all indoor units among thermostat-ON
indoor units.
Keep control:
Except for the above
About detail of
Δ
D signal, refer to P80
Cooling Operation
TeS = TeS initial value + KTe2
KTe2 : Correction value by
Δ
D signal in cooling.
(Q0
3
96)
During compressor frequency PI
control (KTe2 = 0)
Not during compressor frequency PI
control
Keep the current KTe2
Δ
D control
KTe2 = KTe2
□
0.5
KTe2 = KTe2 + 0.5
Up control by
Δ
D signal
continues 120 sec.
Down control by
Δ
D signal
continues 120 sec.
KTe2 = 0
(without correction)
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...