Indoor Unit (RA Models)
SiENBE18-621
88
Function
7.4
Automatic Operation
Automatic Cooling / Heating Function (Heat Pump Only)
When the AUTO mode is selected with the remote control, the microcomputer automatically
determines the operation mode from cooling and heating according to the room temperature
and setting temperature at the time of the operation startup, and automatically operates in that
mode.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature at the main unit setting temperature.
Detailed
Explanation of
the Function
1. Remote control setting temperature is set as automatic cooling / heating setting temperature
(18 to 30°C).
2. Main unit setting temperature equals remote control setting temperature plus correction
value (correction value / cooling: 0 deg, heating: 2 deg.).
3. Operation ON / OFF point and mode switching point are as follows.
1
Heating
→
Cooling switching point:
Room temperature
≥
Main unit setting tempe2.5 deg.
2
Cooling
→
Heating switching point:
Room temperature < Main unit setting temperature –2.5 deg.
3
Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
4. During initial operation
Room temperature
≥
remote control setting temperature: Cooling operation
Room temperature < remote control setting temperature: Heating operation
(R1
3
60)
He
a
ting /
cooling
s
witching point
(He
a
ting thermo
s
t
a
t
OFF point)
M
a
in
u
nit
s
etting
temper
a
t
u
re
(Cooling thermo
s
t
a
t
OFF point)
Cooling /
he
a
ting
s
witching point
Cooling
oper
a
tion
He
a
ting
oper
a
tion
Cooling
oper
a
tion
With compre
ss
or c
a
p
a
city
su
pplied
With no compre
ss
or c
a
p
a
city
su
pplied
2.5 deg.
or higher
(1.5 deg.)
or higher
Le
ss
th
a
n
(1.5 deg.)
2.5 deg.
or higher
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...