16
English
7-4
Press
On/Off
button within 10 sec-
onds, and the test operation starts.
Monitor the operation of the indoor unit
for a minimum of 10 minutes. During
test operation, the indoor unit will
continue to cool regardless of the
temperature setpoint and room
temperature.
Note) In the case of above-men-
∗
tioned procedures
7-3
and
7-4
in reverse order, test
operation can start as well.
Press
7-5
Menu/OK
button in the basic
screen. Main menu is displayed.
In the case of a model having air
fl
ow
7-6
direction function, select
Air
fl
ow Direction
in the main menu
and check that air
fl
ow direction is
actuated according to the setting.
For operation of air
fl
ow direction
setting, see the operation manual.
After the operation of air
fl
ow direction
7-7
is con
fi
rmed, press
Menu/OK
button.
Basic screen returns.
Press and hold
7-8
Cancel
button for
4 seconds or longer in the basic
screen.
Service settings menu is displayed.
Select
7-9
Test Operation
in the service
settings menu, and press
Menu/OK
button. Basic screen returns and
normal operation is conducted.
Note) The test operation will automat-
∗
ically
fi
nish in 30 minuites.
Check the functions according to the
7-10
operation manual.
When the decorative panel is not
7-11
installed, shut off the power supply
after the test operation
fi
nishes.
If construction activities are planned within
●
the space following the test operation
procedure, recommend to the customer
that the air conditioner is not operated to
prevent contamination from paints, drywall
dust and other airborne materials.
4
7-
5
7-
Set temperature
28
°C
Cool
Test Operation
Press
On/Off
button
(within 10 seconds).
Press
Menu/OK
button.
<Main Menu screen>
6
7-
Setting
MainMenu
Airflow Direction
Ventilation
Schedule
Off Timer
Celsius / Fahrenheit
Maintenance Information
1/2
Press
Menu/OK
button.
7
7-
Setting
Airflow Direction
Swing
Change the air
fl
ow
direction by using
(Up/Down)button.
Press
Menu/OK
button.
8
7-
Set temperature
28
°C
Cool
Test Operation
Press and hold
Cancel
button for 4 seconds or
longer during backlight lit.
9
7-
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Press
Menu/OK
button.
<Basic screen>
01_EN_3P243521-3D.indd 16
01_EN_3P243521-3D.indd 16
9/13/2012 7:22:20 PM
9/13/2012 7:22:20 PM
Summary of Contents for BRC1E72
Page 2: ......
Page 24: ...22 English ...
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ...3P243521 3D EM12A024 1209 HT ...