28
NOTICE
•
Installation of optional accessories on the indoor unit may require changes to field settings.
See the manual of the optional accessory.
•
For field setting details related to the indoor unit, see installation manual shipped with the indoor unit.
Field setting mode list
Mode
No.
(Note 1)
FIRST
CODE
NO.
Description
SECOND CODE NO.
(Note 2)
(Items in bold are factory default settings)
01
02
03
04
05
10 (20)
0
Filter
Contamination -
Heavy/Light
(Setting for
spacing time of
display time to
clean air filter)
(Setting for when
filter contamination
is heavy, and
spacing time of
display time to
clean air filter is to
be halved)
Ultra-
long-life
filter
Light
Approx.
10.000 hrs.
Heavy
Approx.
5.000 hrs.
—
—
—
Long-life
filter
Approx.
2.500 hrs.
Approx.
1.250 hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Long-life filter type (Setting
of filter sign indication time).
(Change setting when
Ultra-long-life filter is
installed)
Long-life
filter
Ultra-long-
life filter
—
—
—
2
Thermostat sensor in
remote controller
Use
Not use
—
—
—
3
Spacing time of display
time to clean air filter count
(Setting for when the filter
sign is not to be displayed)
Display
Do not
display
—
—
—
11 (21)
0
Setting number of
connected SPLIT system
simultaneous operation
system indoor units
(Setting for simultaneous
operations system)
Pair
Twin
Triple
Double
twin
—
12 (22)
1
ON/OFF input from outside
(Setting for when forced
ON/OFF is to be operated
from outside).
Forced OFF
ON/OFF
operation
—
—
—
2
Thermostat differential
changeover (Setting for
when using remote
sensor).
1°C
0.5°C
—
—
—
01_EN_EM19A034_IM.indd 28