9
3) Conduct wiring
1. Switch box and transmission wiring are not attached.
2. Do not directly touch the PCB (Printed Circuit Board).
CAUTION
Wiring specifications
Wiring Type
Sheathed vinyl cord or cable (2 cores) (*1)
Wiring Size
0.75~1.25 mm
2
Wiring Length
Max. 500 m (*2)
*
1. Some countries may require a shielded wiring.
Refer to the installation manual attached to the indoor unit.
*
2. This will be the total extended length in the system when doing group control.
Prepare the wiring for connection to the remote controller following these instructions.
Approx.10 mm
For easy wiring, it is better to
keep approx.10 mm difference
between the length of 2 wires.
Cutting guideline
of the wiring
Peel the insulator and sheath
Sheath stripping length:
• Approx. 135 mm for top right outlet
• Approx. 125 mm for right outlet
• Approx. 105 mm for bottom centre outlet
Connect the terminals (P/P1, N/P2) of the remote controller to the terminals (P1, P2) of the indoor
unit. (P1 and P2 have no polarities.)
Top right outlet
P1 P2
Upper case
Lower case
Indoor unit