14
7. Field settings
1)
Press and hold both the Mode
Selector button (
) and the
Temperature Setting (down) button
(
) for 4 seconds or longer.
2)
Select the desired “Mode No.” by
using the Airflow Direction
Adjustment button (
).
For commonly used field setting
items, refer to the table on page 16.
3)
In the case of setting per indoor unit
during group control (when a Mode
No. such as 20, 21, 22, 23 or 25 is
selected), select the “Indoor unit No.”
to be set by using the Fan Speed
Control button (
). (In the case of
group setting, this operation is not
needed.)
4)
Select the FIRST CODE NO. to be
changed by using the Temperature
Setting (up) button (
) and
SECOND CODE NO. to be changed
by using the Temperature Setting
(down) button (
).
Multiple identical mode number
settings are available.
5)
Press the Mode Selector button
(
).
Field setting mode is set.
6)
In the case of multiple setting
changes, repeat
2)
to
4)
.
Press and hold
2 buttons for
4 seconds or longer.
Field setting mode is set
1)
2)
3)
4)
5)
[Basic screen]
[Field setting mode screen]
FIRST CODE NO.
4)
SECOND CODE NO.
01_EN_4P543053-1C.indd 14
10-May-19 4:13:23 PM