16
[Commonly used field setting items]
Mode No.
Note 1)
FIRST
CODE No.
Description of setting
SECOND CODE No.
01
02
03
10(20)
0
Note 3)
Filter Contamination -Heavy/Light
(Setting for spacing time of display
time to clean air filter)
(Setting for when filter contamination
is heavy, and spacing time of display
time to clean air filter is to be halved)
Ultra-long-
life type
Light
Approx.
10,000 Hrs
Hea
vy
Approx.
5,000 Hrs
–
Long life
Filter
Approx.
2,500 Hrs
Approx.
1,250 Hrs
Standard
Filter
Approx.
200 Hrs
Approx.
100 Hrs
1
Note 3)
Long-life filter type
(Setting of filter sign indication time)
(Change setting when Ultra-long-life filter is
installed)
Long-life
filter
Ultra-long-
life filter
–
2
Thermostat sensor in remote controller
Use
Not use
–
11(21)
0
Setting number of connected Sky air simultaneous
operation System indoor unit
(Setting for Simultaneous operation system)
Pair
Twin
–
12(22)
1
ON/OFF input from outside
Forced OFF
ON/OFF
operation
–
13(23)
0
High Ceiling Setting (Setting for when installed in
a Ceiling higher than 2.7m)
* Height depends on the connected model.
Refer to the installation manual attached to the
indoor unit to be connected for details.
≤ 2.7 m*
2.7 m <,
≤ 3.0 m*
3.0 m <,
≤ 3.5 m*
1
Selection of Airflow Direction
(Setting for when a blocking pad kit has been
installed)
4-way flow
3-way flow
2-way flow
3
Airflow Direction Adjustment Function
(To be set when decoration panel for air outlet
installed)
Equipped
No
Equipped
–
4
Airflow Direction Range Setting
Upper
Normal
Lower
6
Setting the External Static pressure
(Setting according to the connected duct
resistance)
(For FHYK, follow the high Ceiling Setting)
Normal
High static
pressure
Low static
pressure
15(25)
1
Humidifying with thermostat OFF
No
Equipped
Equipped
–
3
Drain pump operation with humidifying
No
Equipped
Equipped
–
Note:
1) In case there is a need to perform any setting not listed in the table above, please refer to the
installation manual of each indoor unit.
2) Some functions will be not displayed if the indoor unit is not equipped with that function.
3) This mode is used to set the time until the display time to clean air filter lights up when using a
central remote controller.
01_EN_4P543053-1C.indd 16
10-May-19 4:13:23 PM