Troubleshooting
Troubleshooting Inverter K Series
91
2.15
Outdoor Unit: Actuation of High Pressure Switch
Remote Controller
Display
EEEE3333
Supposed Causes
■
Actuation of outdoor unit high pressure switch
■
Defect of outdoor unit PC board (A1P)
■
Instantaneous power failure
Troubleshooting
∗
1: Actuation of high pressure switch (HPS)
The outdoor unit PC board’s connector is disconnected.
Is the outdoor unit heat exchanger dirty?
Defect of outdoor fan
Is the refrigerant over-charged?
Operation
is normal when turned on
again by remote
controller.
Replace outdoor unit PC board A1P.
Actuation of high pressure switch
∗
1
YES
YES
There was an instantaneous power
failure or a past safety device actuated.
Re-check refrigerant system.
NO
NO
(VF041)
Contact
S1HP (X10A) or S2HP
(X11A) is open.