Troubleshooting
Si-95
96
Troubleshooting Inverter K Series
2.20
Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R3T)
Remote Controller
Display
JJJJ3333
Supposed Causes
■
Defect of thermistor (R3-1T, R3-2T) for outdoor unit discharge pipe
■
Defect of outdoor unit PC board (A1P)
Troubleshooting
The alarm indicator is displayed when the fan is being used also.
(VF046)
Resistance
is normal when
measured after
disconnecting the thermistor
(R3-1T, R3-2T) from the
indoor unit PC board.
(3.5k
Ω
~
400k
Ω
)
Replace outdoor unit PC board A1P.
Connect the thermistor and turn on
again.
NO
NO
Replace the thermistor (R3-1T, R3-2T)
YES
YES
Connector is
connected to X16A, X17A
of outdoor unit PC
board (A1P).