Si-95
Troubleshooting
Troubleshooting Inverter K Series
103
2.27
Negative Phase, Open Phase
Remote Controller
Display
UUU
U1111
Supposed Causes
■
Power supply negative phase
■
Power supply open phase
■
Defect of outdoor PC board A1P
Troubleshooting
(VF053)
Operation
is normal if one place
of power supply line phase is
replaced.
Fix the open phase. Requires
inspection of field power supply section.
Negative phase
Disposal of the problem is completed
by phase replacement.
Replace outdoor unit PC board A1P.
YES
YES
NO
NO
There
is an open phase at
the power supply terminal
section (L1, L2, L3, N) of
the outdoor unit.
SI-95.BOOK Page 103 Friday, March 31, 2000 10:59 AM