Functions
Si-95
34
Functions Inverter K Series
1.19
Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure below).
1.19.1 When the Float Switch is Tripped While the Cooling Thermostat is ON:
∗
1. The objective of residual operation is to completely drain any moisture adhering to the fin of the indoor
unit heat exchanger when the thermostat goes off during cooling operation.
∗
2. One cycle consists of 5 minutes of operation, 5 seconds stop, and another 5 minutes of operation.
1.19.2 When the Float Switch is Tripped During Cooling OFF by Thermostat:
SI-95.BOOK Page 34 Friday, March 31, 2000 10:59 AM