Si-95
Test Operation
Test Operation Inverter K Series
55
<Control input specifications>
■
Input signal
Constant contact a
Input current is approx. 12 - 24 VDC, 10 mA per contact.
Use a micro-current contact for the relay contact.
(Max. 12 VDC, 1 mA)
■
Outside wiring specifications
Recommended electric wiring: Sheathed vinyl cord or cable 0.75
~
1.25 mm
2
(double core)
Wiring length: Max. 150 m
Run separate from power line in order to prevent malfunction.
■
Installation positions
Model/series
Installation box/plate
Installation position
Outdoor
unit
Function unit, EXIII
Not necessary
Inside main unit's electric box
Indoor unit
FXYF~K
KRP1A90
∗
Regarding installation position,
see the page describing the
remote group control adaptor
FXYF~KA
KRP1B98
FXYC~K(L)
KRP1B96
FXYK~K
FXYS~K
FXYM~K
Not necessary
FXYH~K
KRP1B93
FXYA~K
Not necessary
FXYL(M)~K
BSV~K
Not necessary
Inside main unit's electric box
SI-95.BOOK Page 55 Friday, March 31, 2000 10:59 AM