Test Operation
Si-95
72
Test Operation Inverter K Series
Mode No
Function
Contents and operation method
Remote controller display example
4444000
0
Malfunction hysteresis
display
Display malfunction hysteresis.
The hysteresis No. can be changed with the
button.
44441111
Display of sensor and
address data
Display various types of data.
Select the data to be displayed with the
button.
Sensor data
0: Thermostat sensor in remote controller.
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
44443333
Forced fan ON
Manually turn the fan ON by each unit. (When you
want to search for the unit No.)
By selecting the unit No. with the
button, you
can turn the fan of each indoor unit on (forced ON)
individually.
44444444
Individual setting
Set the fan speed and air flow direction by each unit
Select the unit No. with the time mode
button.
Set the fan speed with the
button
Set the air flow direction with the
button.
44445555
Unit No. transfer
Transfer unit No.
Select the unit No. with the
button.
Set the unit No. after transfer with the
button.
4444666
6
This function is not used by VRV System Inverter K Series.
44447777
Hysteresis No: 1 - 9
1: Latest
Unit 1
Malfunction code
2-U4
Malfunction code
40
(VE007)
Temperature ºC
41
Sensor data display
Unit No.
Sensor type
1 1
2 7
Address
41
Address display
Unit No.
Address type
1 8
1
(VE008)
Unit 1
43
(VE009)
Unit 1
Code
44
Air flow direction
P0 - P4
Fan speed 1: Low
3: High
1 3
(VE010)
Unit 1
Code
45
Present unit No.
Unit No. after
transfer
0 2
(VE011)