background image

Installation manual 

BYCQ14 BYCQ140D7GFW1

 

Self cleaning decoration panel

 

4P310441-1C – 2017.05

7

(6) 

Remove the EL. COMP. BOX lid from the indoor unit.  

Refer to 

"5-2 Attaching harness (accessory (4))" on page 4

.

(7) 

Connect the swing lead wire connector to the PCB.

2

1

3

X9A

PCB

Connect the swing lead wire connector to the PCB 

Be sure to connect them securely.

Swing lead wire (to X9A)

(8) 

Attach the EL. COMP. BOX lid in the order opposite to the 

procedure in 

"5-2 Attaching harness (accessory (4))" on 

page 4.

(9) 

Guide the lead wires through the hook.

2

1

Hook

Guide the wires through the hook

6-4  Attaching dust box

1

2

3

4

5

6

7

b

a

Engraved mark on piping side

Panel clasp

Engraved mark on drain side

Panel

Fall prevention cord

Dust box

Mount the dust box with the side where the mark is 

engraved faced downward.

(1) 

Hook the fall prevention cord for the dust box to the panel 

clasp as shown in the illustration.

1

2
3

4
5

Clasp

Hooked fall prevention cord

Panel

Fall prevention cord

Dust box

(2) 

Attach the dust box in the order opposite to the procedure in 

"4-3 Removal of dust box" on page 3.

Note

Make sure that the fall prevention cord is not caught by the 

exhaust opening on the dust box when attaching the dust box. 

Otherwise, the dust box may not function normally.

(3) Turn the fixing knobs (in two points) of the dust box and secure 

the dust box.

(The front side of the panel is shown 
for ease of explanation.)

Fixing 

knob

Fixing 

knob

6-5  Mounting S-shaped pipe (accessory (3))

Mount the dust box side (engraved with A) before mounting the 

brush side (engraved with B).

(Mount them so that the engraved characters will be in conformity.)

Dust box

Dust box

Brush unit

Make sure that 

the engraved 

characters are in 

conformity with 

each other.

2

Claws

(2 points)

Claw

(1 point)

Brush unit

Brush unit side

S-shaped pipe

(accessory (3))

Dust box side

Make sure that the 

engraved characters 

are in conformity with 

each other.

1

Note

Check that the claws are engaged securely. Otherwise, a dust 

collection failure may result.

Summary of Contents for BYCQ140D7GW1

Page 1: ...Decoration Panel Provided with Filter Auto Cleaning Function Self Cleaning decoration panel INSTALLATION MANUAL BYCQ140D7GW1 BYCQ140D7GFW1...

Page 2: ...all the indoor and outdoor units power cord remote controller wiring and transmission wiring at least 1 m away from TV or radio sets This is for the prevention of TV and radio interference Depending o...

Page 3: ...er Be sure to hand the customer the operation manual as well as the installation manual Did you hand the customer the connecting pipe and attachment and ask the customer to keep them Point of operatio...

Page 4: ...the panel together with the accessories attached to the backside of the protective corrugated cardboard Protective corrugated cardboard top The accessories are on the backside Protective corrugated ca...

Page 5: ...tric shock may be received CAUTION Conduct the following work after installing the indoor unit Install the indoor unit according to the installation manual provided with the indoor unit 5 1 Attaching...

Page 6: ...atching brackets of the suction port of the panel on the internal circumference side to the hooks of the indoor unit Note Leave your hands after confirming through the check window that the temporary...

Page 7: ...lation manual of the indoor unit to conduct the work 6 3 Checking panel 1 Remove sealing of panel 1 2 1 2 3 4 1 Remove seal of panel 2 Insert the seal until the seal comes in contact with the claw 3 C...

Page 8: ...illustration 1 2 3 4 5 1 Clasp 2 Hooked fall prevention cord 3 Panel 4 Fall prevention cord 5 Dust box 2 Attach the dust box in the order opposite to the procedure in 4 3 Removal of dust box on page...

Page 9: ...Fall prevention cord Clasp Bend the clasp inward Fall prevention cord 3 Connect the flexible hose accessory 2 onto the panel side The flexible hose accessory 2 has no directionality constraint Flexib...

Page 10: ...nect the flexible hose accessory 2 onto the panel side The flexible hose accessory 2 has no directionality constraint Flexible hose junction on the panel side Fit the claws into the hooks in two point...

Page 11: ...auto cleaning of the self clean panel Operation mode Description 1 Scheduled timer operation Performs filter auto cleaning during the designated period selected from eight periods 2 00 00 to 03 00 op...

Page 12: ...er on The panel will go into initialization operation after the power is turned on 10 3 Conduct the test operation of the panel two minutes after the power is turned on Confirm the cleaning operation...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2012 Daikin 4P310441 1C 2017 05...

Reviews: