5 Configuration
Installation manual
18
C08AA
Daikin hybrid for multi heat pump – heat pump module
4P471756-1C – 2017.10
a
+[8-06]
−[8-06]
b
Ta
Tt
a
Weather-dependent curve
b
Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.
Leaving water temperature: Emitter type
#
Code
Description
[A.3.1.1.7]
[9‑0B]
Emitter type:
Reaction time of the system:
▪ 0: (Quick)
Example:
Small water volume and
fan coils.
▪ 1: (Slow)
Example:
Large water volume, floor
heating loops.
Depending on the system water volume
and the heat emitters type, the heat up
of a space can take longer. This setting
can compensate for a slow or a quick
heating system by adjusting the unit
capacity during the heat up cycle.
Quick heat up function
#
Code
Description
N/A
[C‑0A]
Indoor quick heat up function:
▪ 0: OFF.
▪ 1 (default): On.
Only applicable in case of room
thermostat control. The function will
start up the gas boiler when the actual
room temperature is 3°C lower than the
desired room temperature. The large
boiler capacity can quickly boost up the
room temperature to the desired
temperature. This can be useful after
long periods of absence or after a
breakdown of the system.
Domestic hot water control
Only applicable in case an optional domestic hot water tank is
installed.
#
Code
Description
[A.4.1]
[6-0D]
Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.): Same as 2, but
between the scheduled heatup cycles,
reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated
according to a schedule.
[A.4.5]
[6-0E]
The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
INFORMATION
If a third‑party tank is present in the system ([E‑07]=6), it is
recommended to set [6‑0D] to "0" (i.e. Reheat only).
Contact/helpdesk number
#
Code
Description
[6.3.2]
N/A
Number that users can call in case of
problems.