background image

cm-clic-cf-eng

www.clima-flex.com

22

Control

REFRIGERANT ALARM

The refrigerant alarm is a user-enabled warning that evaluates the 

change in the injection temperature sensor when the compressor 

starts running. If it detects any change in the set time, the alarm 

is activated. 
This alarm will not stop any control process. In this section the 

user can enable and disable the alarm, and if applicable, set the 

minimum detection range and the maximum time in which this 

change must occur to not activate the alarm.

CONDENSING UNIT HIGH TEMPERATURE 

ALARM

This process will only be enabled if the system is air-cooled.

This alarm is triggered when the condenser temperature sensor 

exceeds the value set in this section. This alarm is a warning, so it 

does not affect any control process or stop the compressor.

RESTAURATION

In the last section that can be accessed with the Level 3 password, 

there is the option to reset the unit to factory settings.

Restore System allows the user to reconfigure the system as a 

completely new installation and reset the initial settings. Resetting 

resets the initial system configuration parameters, but does not 

change any of the other values stored in the controller’s memory 

(set points, differential, alarms, etc.).

It is the user’s responsibility to properly configure the system with the new 

settings for proper operation of the units.

 

Note: When the system is reset, the user must restart both 

the controller (pCO) and the terminal (pGD Touch).

ADDENDUM

SERIAL ADDRESS OF EXPANSION MODULES

Each “Child” unit uses an expansion module that communicates 

via Modbus with the parent (pCO) controller through the Fieldbus1 

port of the controller. Consequently, the units need to be configured 

with the correct serial address. To avoid errors, the address 

is set and fixed when the controller is programmed and cannot 

be changed. The only task to be performed by the user is to set 

the physical address of the expansion modules by combining 4 

“switches” on each expansion module. 
The address on the “switches” is set by the 4-bit binary number 

they represent. The lower position of the “switches” has a value of 

“1” and the opposite is “0”.

The addresses to assign are:

PCOE EXPAN-

SION MODULE

SERIAL 

ADDRESS

SWITCHES IN PCOE

CHILD UNIT 1

1

CHILD UNIT 2

2

CHILD UNIT 3

3

CHILD UNIT 4

4

Summary of Contents for Clima-Flex CLIC Series

Page 1: ...Control Manual CLIC Series Air Cooled Fixed Compressor Chilled Ice Water Generator Unit Model 25 to 250 TR Refrigerant HFC 410A 50 60 Hz CM Group Chiller Part Number CM CLIC Date 8 November 2022...

Page 2: ...Clima Flex product at the time of publication and we reserve the right to make changes in design and construction at any time without notice Manufactured in an ISO 9001 certified facility Safety Warni...

Page 3: ...ntial choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry related standards and local state and federal statutes regulations a...

Page 4: ...ITS 1 Stand alone 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 units 8 8 units 9 units 10 10 units CONDENSER FAN A Axial Fixed ANTICORROSION C Coat in Condenser I Coat in Components M Total C...

Page 5: ...commitment to our customers and stakeholders our equipment comes with a 1 year major warranty after start up Our units use R410A refrigerant which is harmless to the ozone layer and is non toxic and...

Page 6: ...er based synthetic coating with ES2 pigment applied to all areas of the coating surface with no bridging of material between fins Therefore ES2 pigments are suitable for even the most corrosive enviro...

Page 7: ...nal belongs to the family of touch screens designed to make the interaction with the pCO system controls easier and more intuitive The electronic technology used and the new 64 000 color display allow...

Page 8: ...ed flow rate and has NO and NC NPN outputs HIGH LOW PRESSURE CONTROL ACB LCB is a small disc type pressure control for use in refrigeration and air conditioning systems As standard it is equipped with...

Page 9: ...OND STAGE NTC NO8 REVERSIBLE VALVE NTC PORT CO AIR HP AIR CO WATER HP WATER TYPE Y1 INVERTER SSR INVERTER SSR 0 10 V PORT CO AIR HP AIR CO WATER HP WATER TYPE B1 INJECTION INJECTION NTC B2 RETURN RETU...

Page 10: ...ital input for this value is a virtual input with a value of 1 or OK if the water flow is acceptable REGULATION Temperature control can be implemented in different ways always taking into account the...

Page 11: ...demand In any configuration the Mother compressor whose capacity is controlled by a drive or a flow valve is the first to start and the last to stop An example of global demand management by starting...

Page 12: ...he freeze alarm but in this alarm the injection sensor reading is considered High Pressure Alarm It is triggered by a Digital input This alarm is a high priority event and stops the compressor operati...

Page 13: ...ble sends user to Alarms page Home Sends the user to the Main Menu Return to Sends the user to the last accessed page Main Menu Sends the user to the Main Menu Alarm log Sends the user to the Alarm Lo...

Page 14: ...of all units will be displayed The properties of the graphs that can be edited are Duration Time Period and maximum and minimum limits Temperature Ranges MENU On the home screen there is a button to...

Page 15: ...e status of the Compressors Independent the mode of operation Cooling or Heating and the status of the Compressors If the control is in Tandem mode it will also show the overall system demand as well...

Page 16: ...units The rotation logic of the units is also enabled Independent Control Ignores the injection and return sensors on the main unit The injection and return temperature readings of the Mother unit wil...

Page 17: ...splayed there are 2 options regular format Day Month Year or US format Month Day Year Note This section is only available for systems configured as Heat Pump WORK HOUR COUNTER The Hours Worked Counter...

Page 18: ...t PID and set the integral time to 0 INDEPENDENT CONTROL The Independent Control calculates all the parameters that regulate the demand control in each unit independently using the injection temperatu...

Page 19: ...blems in your system such as inefficiency and lack of rated capacity For water heat pumps you will see the condenser sensor do not change the maximum and minimum values these must be configured in the...

Page 20: ...r systems with Heat Pump function 1 Enable Defrost Sequence 2 Enable defrost at controller startup 3 Defrost Interval How often defrost is initiated 4 Defrost activation By temperature by defrost By t...

Page 21: ...ic is the same except that one considers the freezing sensor and the other the injection sensor as the main source of information For each of the alarms an activation value a reset and recovery time w...

Page 22: ...t the initial settings Resetting resets the initial system configuration parameters but does not change any of the other values stored in the controller s memory set points differential alarms etc It...

Page 23: ...in place INSTALLATION The equipment to be controlled must be correctly installed according to its user s manual The equipment must be operating normally and must not be in alarm condition CONNECTIVITY...

Page 24: ...of your local area network LAN Along with the Domain Name your equipment has an IP address assigned to it to be controlled and manipulated from inside LAN of your local area network Domain Name Unidad...

Page 25: ...the connection is made you will probably receive a warning that the connection is not Encrypted please disregard this warning as it is not required or necessary to encrypt control sessions with your c...

Page 26: ...Al_Baja_pres_E7 389 DigitalInput Al_Baja_pres_E8 544 DigitalInput Al_Baja_pres_E9 560 DigitalInput Al_congelamiento_E1 28 DigitalInput Al_congelamiento_E10 579 DigitalInput Al_congelamiento_E2 43 Dig...

Page 27: ...talInput ED_sensor_flujo_E8 609 DigitalInput ED_sensor_flujo_E9 630 DigitalInput ED_sensor_flujo_M 163 DigitalInput H_AP_CompE1 5072 AnalogInput H_AP_CompE10 5424 AnalogInput H_AP_CompE2 5084 AnalogIn...

Page 28: ...Input LoadDown_Countdown 5045 AnalogInput Modo_B_C 235 Coil Modulate_Power_Req 88 AnalogInput ON_OFF 142 DigitalInput on_off2 84 Coil Reset_Als 111 Coil Setpoint_cal 91 Holding Setpoint_enf 9 Holding...

Page 29: ...t Temp_ret_E7 194 AnalogInput Temp_ret_E8 235 AnalogInput Temp_ret_E9 242 AnalogInput Temp_ret_Maestro 52 AnalogInput Ventilador_E1 217 DigitalInput Ventilador_E10 647 DigitalInput Ventilador_E2 221 D...

Page 30: ...cm clic cf eng www clima flex com...

Reviews: