iom-clicsa-cf-eng
www.clima-flex.com
38
Index
S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
732
2
S070
REAL
R/W 0
DELTAKEL-
VIN
S070 - Cond.1 frost temp. probe off set
734
2
S071
REAL
R/W 0
DELTAKEL-
VIN
S071 - Cond.2 frost temp. probe off set
736
2
S069
REAL
R/W 0
CELSIUS
S069 - Temperature set point for fan-defrost function
(0=Function disabled)
738
2
UsrDlvW-
Temp_
FromMst
REAL
CELSIUS
Delivery water temperature to user received from Main
(Single evaporator)
740
1
Hc51
USINT(0..11)
R/W 1
Hc51 - Digital output 1 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
741
1
Hc52
USINT(0..11)
R/W 1
Hc52 - Digital output 2 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
742
1
Hc53
USINT(0..11)
R/W 1
Hc53 - Digital output 3 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
743
1
Hc54
USINT(0..11)
R/W 1
Hc54 - Digital output 4 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
744
1
Hc55
USINT(0..11)
R/W 1
Hc55 - Digital output 5 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
745
1
Hc56
USINT(0..11)
R/W 1
Hc56 - Digital output 6 confi g. (0= Not used, 1=Comp. 1 circ.
1, 2=Comp. 2 circ. 1, 3=User heater step 1, 4=User pump 1,
5=Source, 6=Frost heater, 7=4way valve, 8=Oil equal. valve,
9=Freecooling valve, 10=General alarm, 11=User pump 2
746
1
Hc61
USINT(0..8)
R/W 1
Hc61 - Digital output 1 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
747
1
Hc62
USINT(0..8)
R/W 1
Hc62 - Digital output 2 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
748
1
Hc63
USINT(0..8)
R/W 1
Hc63 - Digital output 3 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
749
1
Hc64
USINT(0..8)
R/W 1
Hc64 - Digital output 4 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
750
1
Hc65
USINT(0..8)
R/W 1
Hc65 - Digital output 5 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
751
1
Hc66
USINT(0..8)
R/W 1
Hc66 - Digital output 6 secondary confi g. (0= Not used,
1=Comp. 1 circ. 2, 2=Comp. 2 circ. 2, 3=User heater step 2,
4=User pump 2, 5=Source, 6=Frost heater, 7=4way valve,
8=Oil equal. valve
752
1
Hc31
USINT
R/W 0
Hc31 - Analogue input 1 confi g. (0= Not used, 1= Source
water delivery temp., 2= Outside temp., 3= Discharge temp.,
4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7= Return water temp. from user, 8= Delivery water
temp. to user)
753
1
Hc32
USINT
R/W 0
Hc32 - Analogue input 2 confi g. (0= Not used, 1= Source
water delivery temp., 2= Outside temp., 3= Discharge temp.,
4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7= Return water temp. from user, 8= Delivery water
temp. to user)
754
1
Hc34
USINT
R/W 0
Hc34 - Analogue input 4 confi g. (0= Not used, 1= Source wa-
ter delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing. temp., 5= Suction temp., 6= Evaporation temp.,
7= Condensing press., 8= Evaporating press., 9= Return water
temp. from user, 10= Delivery water temp. to user)
755
1
Hc35
USINT
R/W 0
Hc35 - Analogue input 5 confi g. (0= Not used, 1= Source wa-
ter delivery temp., 2= Outside temp., 3= Discharge temp., 4=
Condensing. temp., 5= Suction temp., 6= Evaporation temp.,
7= Condensing press., 8= Evaporating press., 9= Return water
temp. from user, 10= Delivery water temp. to user)
756
1
Hc41
USINT
R/W 0
Hc41 - Analogue input 1 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
757
1
Hc42
USINT
R/W 0
Hc42 - Analogue input 2 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
Mapping Table