82
SERVICING
READY DVPTC AIRFLOW TABLES
DIP SWITCH SETTING & AIRFLOW TABLE FOR ELECTRIC HEAT
HTR
(kW)
S9
S10
S11
DV25PTCB14 DV29PTCB14 DV35PTCB14
DV37PTCB14 DV33PTCC14 DV39PTCC14 DV49PTCC14 DV37PTCC14 DV59PTCC14 DV37PTCD14 DV59PTCD14 DV49PTCD14** DV61PTCD14*** DV31PTCC14
3
ON ON
ON
550
550
550
600
NR
NR
NR
NR
NR
NR
NR
NR
600
5
ON ON
OFF
650
650
650
700
700
800
700
800
870
990
950
1030
700
6
ON
OFF
ON
700
700
700
780
770
800
770
800
970
1110
1060
1150
770
8
ON
OFF OFF
800
800
800
850
880
950
880
950
1060
1200
1150
1250
880
10
OFF
ON
ON
850
875
875
920
970
1090
970
1090
1120
1240
1220
1320
970
15
OFF
ON
OFF
875
875
1050
950
1090
1290
1090
1290
1220
1520
1520
1650
1090
19*
OFF OFF
ON
NR
NR
NR
NR
1280
1345
1280
1345
NR
NR
NR
NR
1280
20
OFF OFF
ON
NR
NR
NR
NR
NR
NR
NR
NR
1250
1520
NR
1690
NR
21
OFF OFF OFF
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
1750
NR
25
OFF OFF OFF
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
1750
NR
NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation
* Within thermostat user menu CTK0* communicating thermostat will display 20kW for OFF-OFF-ON dip switch selection,
21kW for OFF-OFF-OFF dip switch selection.
NR - Not Rated
** For match up with a 3 Ton outdoor unit:
Airflow for 5kW up to 15kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
***For match up with a 3.5 Ton outdoor unit: Heater Kit application shall not exceed 20kW.
Airflow for 5kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF.