Code Indication on Remote Controller
SiUS121632EA
134
Service Diagnosis
4.3
Outdoor Unit
i
: ON,
h
: OFF,
j
: Blinks
Notes:
1. The error codes in the parenthesis ( ) are displayed only when the system is shut down.
2. When a sensor error occurs, check the remote controller display to determine which sensor is
malfunctioning.
If the remote controller does not indicate the error code, conduct the following procedure.
∗
Turn the power off and then on again. If the same LED indication appears again immediately
after the power is turned on, the fault is in the thermistor.
∗
If the above condition does not result, the fault is in the CT.
3. The indoor unit error code may take the precedence in the remote controller display.
4. Turn the power off and then on again. If the same LED indication appears again, outdoor unit
PCB is faulty. Replace the outdoor unit PCB.
Outdoor Unit LED Indication
Error
Codes
Description
Reference
Page
Green
Red
A
1
2
3
4
5
j
h
h
h
h
h
00
Normal condition
—
UA
Unspecified voltage (between indoor unit and outdoor unit)
UH
Anti-icing control in other rooms
j
h
h
i
i
h
(
U0
)
Refrigerant shortage
j
i
h
h
i
h
U2
Low-voltage detection or over-voltage detection
j
h
i
h
h
h
U3
Wiring Error Check Unexecuted
j
i
h
i
i
h
A5
Anti-icing control for indoor unit
j
i
i
i
h
h
E1
Outdoor unit PCB abnormality
j
i
h
i
h
h
(
E5
)
OL activation (compressor overload)
j
h
i
i
h
h
(
E6
)
Compressor lock
j
i
i
i
i
h
E7
DC fan lock
j
h
i
h
i
h
E8
Input overcurrent detection
j
i
h
h
h
h
EA
Four way valve abnormality
j
i
h
i
h
h
F3
Discharge pipe temperature control
j
i
h
i
i
h
F6
High pressure control in cooling
j
i
i
h
h
h
H0
Compressor sensor system abnormality
H6
Position sensor abnormality
H8
CT or related abnormality
H9
Outdoor temperature thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Outdoor heat exchanger thermistor or related abnormality
J8
Liquid pipe thermistor or related abnormality
J9
Gas pipe thermistor or related abnormality
P4
Radiation fin thermistor or related abnormality
j
i
i
h
i
h
L3
Electrical box temperature rise
j
h
h
h
i
h
L4
Radiation fin temperature rise
j
h
h
i
h
h
L5
Output overcurrent detection
i
—
—
—
—
—
—
See the note 4.
—
h
—
—
—
—
—
—
Check the power supply.
—