11
|
Commissioning
Installer reference guide
48
FTXM20~42+ATXM20~35R2/5V1B + FTXM50~7
ATXM50R2V1B
Daikin room air conditioner
4P518023-8G – 2020.06
11.3 To perform a test run
Prerequisite:
Power supply MUST be in the specified range.
Prerequisite:
Test run may be performed in cooling or heating mode.
Prerequisite:
Test run should be performed in accordance with the operation
manual of the indoor unit to make sure that all functions and parts are working
properly.
1
In cooling mode, select the lowest programmable temperature. In heating
mode, select the highest programmable temperature. Test run can be
disabled if necessary.
2
When the test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
3
The system stops operating 3 minutes after the unit is turned OFF.
11.3.1 To perform a test run using the user interface
1
Press
to switch the system on.
2
Press and
simultaneously.
3
Press
, select and press
.
Result:
Test run operation will stop automatically after about 30 minutes.
4
To stop operation sooner, press
.