D-EOMOAH00903-21_01EN - 16 / 37
(
Available only if pre-heating control
enabled)
Fan Ventilation:
Supply
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Fans setpoints.
Depending on the control type of the fan, the
setpoint can be expressed in
Percentage
[%],
Pascal
[Pa],
Cube meter per hour
[m
3
/h].
(Not available if fans are controlled in On/Off
mode)
Return
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Supply Economy
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Return Economy
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Supply Defrost
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Supply fan setpoint in case of defrost of the
condensing unit ERQ
(Available only if fan-defrost limitation control
enabled)
Return Defrost
0..100 [%]
0..4000[Pa]
0..140000[m
3
/h]
Return fan setpoint in case of defrost of the
condensing unit ERQ
(Available only if fan-defrost limitation control
enabled)
Supply filter #
Warning
# = 1,2,3,4
0..1000 Pa
Differential Pressure threshold for Warning
on supply filter # Alarm
Return filter #
Warning
# = 1,2
0..1000 Pa
Differential Pressure threshold for Warning
on return filter # Alarm
Others:
Dehumidification
-
0…100 [%rH]
-
Humidification…100 [%rH]
(if humidification
control enabled)
Dehumidification setpoint
(
Available only if dehumidification control
enabled)
Humidification
-
0…100 [%rH]
-
0…Dehumidification [%rH]
(if dehumidification
control enabled)
Humidification setpoint.
(Available only if humidification control
enabled)
Air Quality
0..3000 [ppm]
Air control quality setpoint. Limit of ppm (parts
per million) for the CO
2
.
(Available only if
CO
2
control enabled)
Fan fire
setpoint
0..100 [%]
Fans setpoints when fire alarm detected.
(Available only if Fire Alarm enabled)