D-EOMOAH00903-21_01EN - 30 / 37
7
Modbus nodes diagnostic and alarms
Led #
Color
Manager
State
Meaning
1
Green
Board firmware
Alive
Node is powered on
2
Red
Board firmware
Hardware Error
The firmware has detected an EEPROM error.
If this error occurs the Node must be removed
and replaced. Contact factory.
3
Yellow
Board firmware
I/O Error
The firmware has detected an error in the I/O
of the Node.
4
Blue
MT4 / DStream
Communication OK
Modbus communication is established and is
properly operating
5
Yellow
MT4 / DStream
Not Used
Not Used
6
Red
MT4 / DStream
Not Used
Not Used
7.1
Node#HardwareErr
Description
The firmware has detected an EEPROM error.
Notification
MT4, LED 2 (Red)
Delay
No
Reset type
Automatic
Countermeasure
Replacement, contact factory.
7.2
Node#CommErr
Description
The node # is offline from the Modbus communication
Notification
MT4, LED 5 (Yellow)
Delay
10sec
Reset type
Automatic
Countermeasure
Node# could be offline because of a Hardware Error or because is not powered on (Led alive
off). If not in the preceding cases, check Modbus cable connection to the node. If all nodes are
in communication error state, check integrity of root connection to MT4.
7.3
Node#InOutErr
Description
On node # an I/O error has occurred. This could mean:
•
AIN1 fault - Open Loop/ Short Circuit
•
AIN2 fault - Open Loop/ Short Circuit
•
AIN3 fault - Open Loop/ Short Circuit
•
I/O general purpose fault - Open Loop/ Short Circuit
•
AO1 fault
•
AO2 fault
•
AO3 (I/O general purpose) FAULT
Notification
MT4, LED 3 (Yellow)
Delay
No
Reset type
Automatic
Countermeasure
Check connection/integrity of probes/actuators
7.4
Node#DP1Err
Description
Differential pressure transducer #1
Notification
MT4
Delay
No
Reset type
Automatic
Countermeasure
Check polarity of flow tubes (+/-). Check connection/integrity of transducer board
1
2
3
4
5
6