Protection Control
Si18-525B
122
Function
4.2
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
In cooling operation
In heating operation
Pe
<
0.25MPa
52Hz
SVP=OFF
SVP=ON
Pe
>
0.4MPa
Pe
<
0.15MPa
Pe
>
0.30MPa
Pe
<
0.07MPa
Low pressure not limited
Low pressure
standby
Low pressure
limited
Pe: LP pressure sensor detection
value
When occurring 3 times within 60 min.,
the malfunction code "E4" is output.
(Q0376)
Pe
<
0.07MPa
Upper limit:
124Hz
Upper limit:
52Hz
Upper limit: 1-step up from
current compressor frequency
(V3176)
&
• Pe>0.25MPa
• INV upper limit
frequency
&
More than 124Hz
Pe<0.16MPa
SVP = OFF
SVP = ON
Low pressure not limited
Low pressure
standby
Low pressure limited
Pe>0.19MPa(every 20 sec.)
Pe>0.17MPa
Pe<0.13MPa
Pe<0.13MPa
Pe<0.16MPa
Pe<0.10MPa
Pe>0.19MPa
When occurring 3 times within 60 min.,
the malfunction code "E4" is output.
Pe: LP pressure sensor detection
value
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...