Si18-525B
Field Setting
Test Operation
169
No.
Setting item
Description
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
21
Refrigerant
collection mode
setting
Sets to refrigerant collection mode.
22
Night quiet mode
setting
Sets automatic Night quiet operation in a simple way.
The operating time is based on “Starting set” and “Ending
set”.
26
Night quiet mode
control starting
setting
Sets starting time of Night quiet operation. (Night quiet
mode setting is also required.)
27
Night quiet mode
control ending
setting
Sets ending time of Night quiet operation. (Night quiet
mode setting is also required.)
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and Night quiet operation.
30
Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
31
Demand setting 2
Changes target value of power consumption when
demand control 2 is input.
32
Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.
b. “Setting mode 2”
<Selection of setting items>
<Selection of setting conditions>
Push and hold the MODE button
(BS1) for 5 seconds and set to
“Setting mode 2”.
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
Push the SET button (BS2) and set
to the setting condition you want.
↓
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of “Setting
mode 2”.
∗
If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
(V2764)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...