Field Setting for SkyAir Indoor Unit
Si18-525B
186
Test Operation
4.5
Detailed Explanation of Setting Modes
4.5.1
Air Flow Direction
Setting (FFQ, FCQ)
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
4.5.2
Filter Sign
Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
4.5.3
Range of Air Flow Direction
Setting (FFQ, FCQ)
Make the following air flow direction setting according to the respective purpose.
4.5.4 Fan Speed OFF When Thermostat is OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting
to “Fan OFF.”
∗
Used as a countermeasure against odor for barber shops and restaurants.
Setting Table
Mode No.
First Code No.
Second Code
No.
Setting
13 (23)
1
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Filter Specs.
Setting
Long Life
Contamination Light
01
2,500
Contamination Heavy
02
1,250
Mode No.
First Code No.
Second Code No.
Setting
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling
prevention)
Mode No.
First Code No.
Second Code No.
Setting
11(21)
2
01
—
02
Fan OFF
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...