Service Check Function
Si18-525B
324
Troubleshooting
2.5
Sky Air Indoor Unit Error Codes and LED Indication
Symbols
5
: Blinks
4
: On
3
: Off — : No connection with troubleshooting
: High probability of malfunction
: Possibility of malfunction
: Low probability of malfunction
— : No possibility of malfunction (do not replace)
System
Indoor Unit
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
U5
—
Transmission error (between
indoor and remote controller)
U8
—
Transmission error between
“main” remote controller and
“sub” remote controller
UA
—
—
Excessive indoor units
connected to this system.
Indoor
Unit
LED
Display
(H1P)
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
5
—
—
—
—
Normal
→
to outdoor unit
—
5
A1
—
—
—
Failure of indoor unit PC
board (For self-diagnosis by
LED, refer to p.314.)
4
3
5
A3
—
—
—
Malfunction of drain water
level system
5
AF
—
—
—
Float switch operation
during compressor stop
5
A6
(FHQ only)
—
—
Indoor unit fan motor
overload / overcurrent / lock
5
A7
—
—
Swing flap motor
Malfunction / Lock
5
AJ
—
—
Failure of capacity setting
5
C4
—
—
Malfunction of heat
exchanger temperature
sensor system (R2T)
5
C5
—
—
Malfunction of heat
exchanger temperature
sensor system (R3T)
5
C9
—
—
Malfunction of suction air
temperature sensor system
5
CJ
—
—
—
Malfunction of remote
control air temperature
sensor system
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...