List of Malfunction Code
Troubleshooting
327
3. List of
Malfunction Code
9
: Blink
8
: ON
7
: OFF
Malfunction
code
Malfunction contents
Page Referred
RA Indoor
Unit
SkyAir
Indoor Unit
BP Unit
Outdoor
Unit
Indoor
Unit
A0
Error of external protection device
—
—
—
—
A1
PC board defect, E
2
PROM defect
—
—
A3
Malfunction of drain level control system (33H)
—
—
—
A5
Freeze-up protection or high pressure control
—
—
—
A6
Fan motor (MF) lock, overload
—
—
A7
Malfunction of swing flap motor (MA)
—
—
—
A9
Malfunction of electronic expansion valve (20E)
—
—
—
AF
Drain pump error
—
—
—
AJ
Malfunction of capacity setting
—
—
—
C4
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
C5
Malfunction of thermistor (R3T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
—
C7
Shutter drive motor / shutter limit switch abnormality
—
—
—
C9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
—
—
CA
Malfunction of thermistor for air outlet (loose
connection, disconnection, short circuit, failure)
—
—
—
—
CJ
Malfunction of thermostat sensor in remote controller
—
—
—
Outdoor
Unit
E1
PC board defect, E
2
PROM defect
—
—
—
E2
Faulty BP unit PCB
—
—
—
E3
Actuation of high pressure switch
—
—
—
E4
Actuation of low pressure switch
—
—
—
E5
Compressor motor lock
—
—
—
E6
Standard compressor lock or over current
—
—
—
—
E7
Malfunction of outdoor unit fan motor
—
—
—
E9
Malfunction of moving part of electronic expansion
valve (Y1E~2E)
—
—
—
F3
Abnormal discharge pipe temperature
—
—
—
F6
Refrigerant overcharged
—
—
—
—
H3
Malfunction of high pressure switch
—
—
—
—
H4
Actuation of low pressure switch
—
—
—
—
H7
Abnormal outdoor fan motor signal
—
—
—
—
H9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
—
—
—
J0
Faulty BP liquid or gas pipe thermistor
—
—
—
J2
Current sensor malfunction
—
—
—
—
J3
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
—
—
—
J5
Malfunction of thermistor (R2T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
—
—
—
J6
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
—
J7
Malfunction of header thermistor
—
—
—
—
J8
Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
—
—
—
—
J9
Malfunction of receiver gas pipe thermistor (R5T)
—
—
—
JA
Malfunction of discharge pipe pressure sensor
—
—
—
JC
Malfunction of suction pipe pressure sensor
—
—
—
L0
Inverter system error
—
—
—
—
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...