Troubleshooting for BP Unit
Troubleshooting
359
6. Troubleshooting for BP Unit
6.1
Malfunction of Electronic Expansion Valve
Remote
Controller
Display
A9
Method of
Malfunction
Detection
Detection by checking continuity and lack of connector.
Malfunction
Decision
Conditions
Malfunction is determined by no common voltage applied when turning the power supply on.
Supposed
Causes
Faulty harness of electronic expansion valve
Incorrect connectors connection of electronic expansion valve
Troubleshooting
Turn the power supply off once
and then back on.
Keep using as it is. (Could
be outside error other than
malfunction.)
Correct the connection.
Electronic expansion valve
coil faulty
Replace BP unit PCB of the
applicable part.
Is malfunction
re-generated?
Is the
resistance of the
electronic expansion
valve coil normal?
(46±4
Ω
/20˚C)
(Q0390)
NO
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
YES
Is the
electronic
expansion valve coil
connected to PCB
of the faulty
part?
NO
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...